IST7 60–200 · Three-phase UPS
IST7-100 Three-phase online UPS 100 kVA, 400 V
The IST7-100 is a 100 kVA / 100 kW three-phase online double-conversion UPS in a 400 mm wide cabinet, upgradable to 120 kVA from the display. For data centres, hospitals and plants with about 100 kW of critical load, alone or in parallel systems of up to eight units.
Quick answers
IST7-100: quick answers
- What it is
- The IST7-100 is a 100 kVA / 100 kW three-phase online double-conversion UPS in a 400 mm wide cabinet, upgradable to 120 kVA from the display.
- Who it is for
- For data centres, hospitals and plants with about 100 kW of critical load, alone or in parallel systems of up to eight units.
- Supply and configuration
- 3 phases + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Battery and backup
- ±216 V
- Size and weight
- 400 × 960 × 1193 mm · 165 kg
- Ordering code
- IST7-100
IST7 60–200
What sets apart the IST7-100
One hundred kilowatts on 0.38 m² of floor: the IST7-100 is 400 × 960 × 1193 mm and 165 kg. The catalogue's operating-cost example is built on a 100 kW load: at the 96.5% peak efficiency the losses are 3.6 kW, about 31,800 kWh a year, and in ECO mode at 99% they drop to 1.0 kW, about 8,850 kWh.
Its default battery is ±216 V, 36 blocks of 12 V, drawing 241 A nominal and 279 A maximum on 50 mm² cables. The charger gives up to 30 A, and the charge current limit is 0.2 C for lead-acid and 0.5 C for lithium.
- Against the IST7-80 (one size down): Rated power 100 kVA / 100 kW against 80 kVA / 80 kW; Capacity upgrade to 120 against to 100 / 120; Nominal DC voltage (default) ±216 V against ±192 V; Weight 165 kg against 163 kg.
- Against the IST7-120 (one size up): Rated power 100 kVA / 100 kW against 120 kVA / 120 kW; Weight 165 kg against 167 kg.
Planning data
IST7-100: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-100.
Front, rear and footprint
| Model | W × D × H (mm) | Weight |
|---|---|---|
| IST7-100 | 400 × 960 × 1193 | 165 kg |
BB5 to BB8, matched to every IST7
| UPS | IST7-80 · 100 · 120 |
|---|---|
| BB5 | — |
| BB6 | 30–36 × 60 Ah |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 60 / 64 × 80 / 100 Ah |
| 2 × BB8 | 120 / 128 × 80 / 100 Ah |
Battery connection by UPS model
| UPS | IST7-100 |
|---|---|
| I nom. (A) | 241 |
| I max. (A) | 279 |
| +/N/− mm² | 50 |
| PE mm² | 35 |
Installation
Installing the IST7-100: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 800 mm, left 800 mm, right 800 mm, top 800 mm | AEC IST7 60–200 user manual p.35 §3.2.3 |
| Cable entry | Bottom, through the base | AEC IST7 60–200 user manual |
| Heat at full load | 3.63 kW at 100 kW load, 96.5 % efficiency | AEC IST7 60–200 user manual p.87 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–30 °C | AEC IST7 60–200 user manual p.34–35 §3.2.2 |
| Switches and terminals | Mains, bypass, output and maintenance bypass switches behind the lockable front door; terminals behind the front and rear wiring covers. | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
| Door | One leaf, hinged on the right | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
Size and floor
How big it is
400 × 960 × 1193 mm · 165 kg.
Floor load = weight ÷ footprint (165 kg).
Efficiency
How efficient is the AEC IST7-100 at your load?
IST7-100, 100 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 1.07 kW (η 95.9%) · 50%: 1.81 kW (η 96.5%) · 75%: 2.96 kW (η 96.2%) · 100%: 4.28 kW (η 95.9%). At 50% load, 24/7, it loses about 15,886 kWh a year.
How the curve is drawn and where each figure comes from: the IST7 60–200 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9% | Typical curve, derived from the datasheet efficiency of 96.5% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.
Drag to turnIn 3D
Look around the IST7-100
The turntable shows the IST7-120; the full 3D view opens on the IST7-100.
Technical data
Technical data IST7-100
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW) | 100 |
| Capacity upgrade | to 120 |
| Input | |
| Connection | 3 phases + N + PE |
| Rated voltage | 220 / 230 / 240 V phase (380 / 400 / 415 V line) |
| Voltage range | 187–280 V phase at full power · 80–186 V with linear derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass synchronisation range | 50 / 60 Hz ± 6 Hz |
| Battery | |
| Nominal DC voltage (default) | ±216 V |
| String length | 28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card) |
| Max. charge current | 30 A |
| Output | |
| Voltage · frequency | 220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery) |
| Power factor · THDv | 1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load |
| Transient · unbalance · phase error | ≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1° |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 15 ms not synchronised |
| Inverter overload | ≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate) |
| Bypass overload | ≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms |
| System | |
| Efficiency AC/AC | up to 96.5% double conversion · 99% ECO mode |
| Parallel | Up to 8 units, capacity or N+X · BSC dual-bus synchronisation |
| Communication | RS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot |
| Display | Colour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries |
| Environment | −5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling |
| Cable entry | bottom (all models) |
| EMC | IEC 62040-2:2016 · category C3 (not for residential use without additional measures) |
| Dimensions W × D × H | 400 × 960 × 1193 mm |
| Weight | 165 kg |
| Item | IST7-100 |
|---|---|
| Rated power (kVA / kW) | 100 |
| Capacity upgrade | to 120 |
| Power units | 1 |
| Nominal DC voltage (default) | ±216 V |
| Max. charge current | 30 A |
| W × D × H (mm) | 400 × 960 × 1193 |
| Weight | 165 kg |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST7-100
| Code | Description |
|---|---|
| IST7-100 | 100 kVA, upgradable to 120 kVA |
| PAR-IST7-60/200 | Parallel kit |
| IST7-[kVA]-[n]X[Ah] | UPS with battery cabinet, n × 12 V [Ah] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah) |
Questions
Questions about the IST7-100
How much energy does the IST7-100 lose at full load?
At 100 kW, 24/7, the catalogue gives 3.6 kW of losses and 31,800 kWh a year in double conversion at 96.5%, and 1.0 kW and 8,850 kWh in ECO mode at 99%. Room cooling comes on top; the values are indicative.
Can IST7-100 units share one battery?
Yes: the units of a parallel system can share a common battery bank, or each keep its own. Up to eight units run on one load bus with the parallel kit PAR-IST7-60/200, current sharing within 5%.
How long does a 100 kVA UPS like the IST7-100 run?
2 to 50 minutes at full load (100 kW), and 5 to 117 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 30 × 12 V 60 Ah (IST7-100-30X60): 2 minutes at 100% and 5 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST7-100 and how much does it weigh?
The AEC IST7-100 measures 400 × 960 × 1193 mm; weight: 165 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST7-100?
In the EMEA 2026 catalogue the AEC IST7-100 is listed as IST7-100; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST7-100: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.