IST7 60–200 · Three-phase UPS

IST7-200 Three-phase online UPS 200 kVA, 400 V

VRLA200 kVAthree-phase online UPS, 400 V

The IST7-200 is a 200 kVA / 200 kW three-phase online double-conversion UPS, the largest IST7, with two power units in a 600 × 1000 × 1600 mm cabinet of 296 kg. For data centres, hospitals and industry with 160 to 200 kW per unit, or up to 1.6 MW with eight units in parallel.

200 kVA / 200 kWRating
600 × 1000 × 1600 mmW × D × H
296 kgWeight
±216 VBattery

Quick answers

IST7-200: quick answers

What it is
The IST7-200 is a 200 kVA / 200 kW three-phase online double-conversion UPS, the largest IST7, with two power units in a 600 × 1000 × 1600 mm cabinet of 296 kg.
Who it is for
For data centres, hospitals and industry with 160 to 200 kW per unit, or up to 1.6 MW with eight units in parallel.
Supply and configuration
3 phases + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Battery and backup
±216 V
Size and weight
600 × 1000 × 1600 mm · 296 kg
Ordering code
IST7-200

IST7 60–200

What sets apart the IST7-200

Eight IST7-200 in parallel make 1.6 MW, the ceiling of the range, in capacity or N+X redundant systems; BSC synchronisation links two independent systems for dual-bus loads. Each unit draws up to 558 A from the battery (482 A nominal) on 95 mm² cables, and the catalogue pairs it only with BB8 cabinets, one or two.

Like every IST7 60–200 it reaches 96.5% peak efficiency in double conversion and 99% in ECO, with a PFC rectifier (THDi ≤ 3%) that keeps the upstream transformer and generator lightly stressed. Generator mode limits the charge power while on a genset.

  • Against the IST7-160 (one size down): Rated power 200 kVA / 200 kW against 160 kVA / 160 kW; Weight 296 kg against 294 kg.

Planning data

IST7-200: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-200.

Front, rear and footprint

IST7-200 · Front, rear and footprint
ModelW × D × H (mm)Weight
IST7-200600 × 1000 × 1600296 kg

BB5 to BB8, matched to every IST7

IST7-200 · BB5 to BB8, matched to every IST7
UPSIST7-200
BB5—
BB6—
BB7—
BB860 / 64 × 80 / 100 Ah
2 × BB8120 / 128 × 80 / 100 Ah

Battery connection by UPS model

IST7-200 · Battery connection by UPS model
UPSIST7-200
I nom. (A)482
I max. (A)558
+/N/− mm²95
PE mm²70

Installation

Installing the IST7-200: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST7-200 · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, left 800 mm, right 800 mm, top 800 mmAEC IST7 60–200 user manual p.35 §3.2.3
Cable entryBottom, through the baseAEC IST7 60–200 user manual
Cooling air2,420 m³/hEMEA 2026 catalogue p.157
Heat at full load7.25 kW at 200 kW load, 96.5 % efficiencyAEC IST7 60–200 user manual p.87 §A; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °C, best 20–30 °CAEC IST7 60–200 user manual p.34–35 §3.2.2
Switches and terminalsMains, bypass, output and maintenance bypass switches behind the lockable front door; terminals behind the front and rear wiring covers.AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge)
DoorOne leaf, hinged on the rightAEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge)

Size and floor

How big it is

600 × 1000 × 1600 mm · 296 kg.

0.6 m²footprint
493 kg/m²floor load
1.6 mheight

Floor load = weight ÷ footprint (296 kg).

1.75 mFrontSide60010001600

Efficiency

How efficient is the AEC IST7-200 at your load?

IST7-200, 200 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 2.14 kW (η 95.9%) · 50%: 3.63 kW (η 96.5%) · 75%: 5.93 kW (η 96.2%) · 100%: 8.55 kW (η 95.9%). At 50% load, 24/7, it loses about 31,772 kWh a year.

96.5%50% · Typical curve, derived from the datasheet efficiency of 96.5% (AEC method)

How the curve is drawn and where each figure comes from: the IST7 60–200 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9%Typical curve, derived from the datasheet efficiency of 96.5% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.

AEC IST7-200, rendered from its 3D modelDrag to turn

In 3D

Look around the IST7-200

Technical data

Technical data IST7-200

Only this model's values, from the EMEA 2026 catalogue table.

IST7-200 · Technical data
General
Rated power (kVA / kW)200
Input
Connection3 phases + N + PE
Rated voltage220 / 230 / 240 V phase (380 / 400 / 415 V line)
Voltage range187–280 V phase at full power · 80–186 V with linear derating
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 3% at full load
Bypass synchronisation range50 / 60 Hz ± 6 Hz
Battery
Nominal DC voltage (default)±216 V
String length28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card)
Max. charge current60 A
Output
Voltage · frequency220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery)
Power factor · THDv1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load
Transient · unbalance · phase error≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1°
Transfer time inverter ↔ bypass< 1 ms synchronised · < 15 ms not synchronised
Inverter overload≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate)
Bypass overload≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms
System
Efficiency AC/ACup to 96.5% double conversion · 99% ECO mode
ParallelUp to 8 units, capacity or N+X · BSC dual-bus synchronisation
CommunicationRS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot
DisplayColour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries
Environment−5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling
Cable entrybottom (all models)
EMCIEC 62040-2:2016 · category C3 (not for residential use without additional measures)
Dimensions W × D × H600 × 1000 × 1600 mm
Weight296 kg
IST7-200 · Models
ItemIST7-200
Rated power (kVA / kW)200
Capacity upgrade—
Power units2
Nominal DC voltage (default)±216 V
Max. charge current60 A
W × D × H (mm)600 × 1000 × 1600
Weight296 kg

Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST7-200

Ordering codes IST7-200
CodeDescription
IST7-200200 kVA / 200 kW
PAR-IST7-60/200Parallel kit
IST7-[kVA]-[n]X[Ah]UPS with battery cabinet, n × 12 V [Ah] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah)

Questions

Questions about the IST7-200

How many IST7-200 can run in parallel?

Up to eight, for 1.6 MW, with parallel cables in a ring (N units, N cables) and addresses 1–8 set from the display. A parameter match page shows any setting that differs between units and copies it to all.

Which batteries suit the IST7-200?

The catalogue lists BB8 with 60 / 64 × 80 / 100 Ah or two BB8 with 120 / 128 × 80 / 100 Ah, the string split at the neutral (+, N, −). Lithium cabinets are available on request with the BMS card.

How long does a 200 kVA UPS like the IST7-200 run?

3 to 19 minutes at full load (200 kW), and 8 to 50 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 60 × 12 V 80 Ah · 2 × 30 (IST7-200-60X80): 4 minutes at 100% and 10 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST7-200 and how much does it weigh?

The AEC IST7-200 measures 600 × 1000 × 1600 mm; weight: 296 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

What is the ordering code of the AEC IST7-200?

In the EMEA 2026 catalogue the AEC IST7-200 is listed as IST7-200; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST7-200: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.