IST7 60–200 · Three-phase UPS
IST7-200 Three-phase online UPS 200 kVA, 400 V
The IST7-200 is a 200 kVA / 200 kW three-phase online double-conversion UPS, the largest IST7, with two power units in a 600 × 1000 × 1600 mm cabinet of 296 kg. For data centres, hospitals and industry with 160 to 200 kW per unit, or up to 1.6 MW with eight units in parallel.
Quick answers
IST7-200: quick answers
- What it is
- The IST7-200 is a 200 kVA / 200 kW three-phase online double-conversion UPS, the largest IST7, with two power units in a 600 × 1000 × 1600 mm cabinet of 296 kg.
- Who it is for
- For data centres, hospitals and industry with 160 to 200 kW per unit, or up to 1.6 MW with eight units in parallel.
- Supply and configuration
- 3 phases + N + PE · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
- Battery and backup
- ±216 V
- Size and weight
- 600 × 1000 × 1600 mm · 296 kg
- Ordering code
- IST7-200
IST7 60–200
What sets apart the IST7-200
Eight IST7-200 in parallel make 1.6 MW, the ceiling of the range, in capacity or N+X redundant systems; BSC synchronisation links two independent systems for dual-bus loads. Each unit draws up to 558 A from the battery (482 A nominal) on 95 mm² cables, and the catalogue pairs it only with BB8 cabinets, one or two.
Like every IST7 60–200 it reaches 96.5% peak efficiency in double conversion and 99% in ECO, with a PFC rectifier (THDi ≤ 3%) that keeps the upstream transformer and generator lightly stressed. Generator mode limits the charge power while on a genset.
- Against the IST7-160 (one size down): Rated power 200 kVA / 200 kW against 160 kVA / 160 kW; Weight 296 kg against 294 kg.
Planning data
IST7-200: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-200.
Front, rear and footprint
| Model | W × D × H (mm) | Weight |
|---|---|---|
| IST7-200 | 600 × 1000 × 1600 | 296 kg |
BB5 to BB8, matched to every IST7
| UPS | IST7-200 |
|---|---|
| BB5 | — |
| BB6 | — |
| BB7 | — |
| BB8 | 60 / 64 × 80 / 100 Ah |
| 2 × BB8 | 120 / 128 × 80 / 100 Ah |
Battery connection by UPS model
| UPS | IST7-200 |
|---|---|
| I nom. (A) | 482 |
| I max. (A) | 558 |
| +/N/− mm² | 95 |
| PE mm² | 70 |
Installation
Installing the IST7-200: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 800 mm, left 800 mm, right 800 mm, top 800 mm | AEC IST7 60–200 user manual p.35 §3.2.3 |
| Cable entry | Bottom, through the base | AEC IST7 60–200 user manual |
| Cooling air | 2,420 m³/h | EMEA 2026 catalogue p.157 |
| Heat at full load | 7.25 kW at 200 kW load, 96.5 % efficiency | AEC IST7 60–200 user manual p.87 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–30 °C | AEC IST7 60–200 user manual p.34–35 §3.2.2 |
| Switches and terminals | Mains, bypass, output and maintenance bypass switches behind the lockable front door; terminals behind the front and rear wiring covers. | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
| Door | One leaf, hinged on the right | AEC IST7 60–200 user manual p.13 Fig. 2-2/2-3 (handle on the left edge) |
Size and floor
How big it is
600 × 1000 × 1600 mm · 296 kg.
Floor load = weight ÷ footprint (296 kg).
Efficiency
How efficient is the AEC IST7-200 at your load?
IST7-200, 200 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 2.14 kW (η 95.9%) · 50%: 3.63 kW (η 96.5%) · 75%: 5.93 kW (η 96.2%) · 100%: 8.55 kW (η 95.9%). At 50% load, 24/7, it loses about 31,772 kWh a year.
How the curve is drawn and where each figure comes from: the IST7 60–200 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9% | Typical curve, derived from the datasheet efficiency of 96.5% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.
Drag to turnTechnical data
Technical data IST7-200
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW) | 200 |
| Input | |
| Connection | 3 phases + N + PE |
| Rated voltage | 220 / 230 / 240 V phase (380 / 400 / 415 V line) |
| Voltage range | 187–280 V phase at full power · 80–186 V with linear derating |
| Frequency · power factor · THDi | 40–70 Hz · ≥ 0.99 · ≤ 3% at full load |
| Bypass synchronisation range | 50 / 60 Hz ± 6 Hz |
| Battery | |
| Nominal DC voltage (default) | ±216 V |
| String length | 28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card) |
| Max. charge current | 60 A |
| Output | |
| Voltage · frequency | 220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery) |
| Power factor · THDv | 1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load |
| Transient · unbalance · phase error | ≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1° |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 15 ms not synchronised |
| Inverter overload | ≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate) |
| Bypass overload | ≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms |
| System | |
| Efficiency AC/AC | up to 96.5% double conversion · 99% ECO mode |
| Parallel | Up to 8 units, capacity or N+X · BSC dual-bus synchronisation |
| Communication | RS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot |
| Display | Colour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries |
| Environment | −5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling |
| Cable entry | bottom (all models) |
| EMC | IEC 62040-2:2016 · category C3 (not for residential use without additional measures) |
| Dimensions W × D × H | 600 × 1000 × 1600 mm |
| Weight | 296 kg |
| Item | IST7-200 |
|---|---|
| Rated power (kVA / kW) | 200 |
| Capacity upgrade | — |
| Power units | 2 |
| Nominal DC voltage (default) | ±216 V |
| Max. charge current | 60 A |
| W × D × H (mm) | 600 × 1000 × 1600 |
| Weight | 296 kg |
Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST7-200
| Code | Description |
|---|---|
| IST7-200 | 200 kVA / 200 kW |
| PAR-IST7-60/200 | Parallel kit |
| IST7-[kVA]-[n]X[Ah] | UPS with battery cabinet, n × 12 V [Ah] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah) |
Questions
Questions about the IST7-200
How many IST7-200 can run in parallel?
Up to eight, for 1.6 MW, with parallel cables in a ring (N units, N cables) and addresses 1–8 set from the display. A parameter match page shows any setting that differs between units and copies it to all.
Which batteries suit the IST7-200?
The catalogue lists BB8 with 60 / 64 × 80 / 100 Ah or two BB8 with 120 / 128 × 80 / 100 Ah, the string split at the neutral (+, N, −). Lithium cabinets are available on request with the BMS card.
How long does a 200 kVA UPS like the IST7-200 run?
3 to 19 minutes at full load (200 kW), and 8 to 50 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 60 × 12 V 80 Ah · 2 × 30 (IST7-200-60X80): 4 minutes at 100% and 10 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST7-200 and how much does it weigh?
The AEC IST7-200 measures 600 × 1000 × 1600 mm; weight: 296 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST7-200?
In the EMEA 2026 catalogue the AEC IST7-200 is listed as IST7-200; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST7-200: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.