Choosing, sizing and ordering 5 questions

Can IST3-J units run in parallel?

Only the 10 kVA /B version can be used in parallel, through its parallel port. The other models work as single units.

Answered on IST3-J

Can two IST3-J 10 kVA run in parallel?

Yes, with the 10 kVA /B parallel version, which has its own parallel port on the rear panel. The 6 kVA and the 1–3 kVA models have no parallel version.

Answered on IST3-J 10 kVA

How many BBJ2 cabinets can the IST3-J 10 kVA take?

One to eight, that is 16 to 128 batteries of 12 V 9 Ah (codes IST3J-6/10-[n]X9). Each BBJ2 is 3U, 438 × 500 mm and 10 kg empty, and goes below the UPS in the rack.

Answered on IST3-J 10 kVA

IST3-J: what is the ordering code of each model?

As the EMEA 2026 catalogue lists them:

ModelCatalogue code
IST3-J 1 kVAIST3J-1-3X9
IST3-J 2 kVAIST3J-2-4X9
IST3-J 3 kVAIST3J-3-6X9
IST3-J 6 kVAIST3J-6, IST3J-6/10-[n]X9
IST3-J 10 kVAIST3J-10, IST3J-6/10-[n]X9

AEC gives the full code, batteries included, from the load and the backup time.

Each model's own page, linked in the table, gives its full answer and data.

What are the input limits of the IST3-J 1 kVA?

176–295 V above 75% load, 154–176 V at 50–75% and 120–154 V below 50%: at light load the battery is not touched down to 120 V. The maximum input current is 6 A, on a 10 A breaker.

Answered on IST3-J 1 kVA

Backup time and batteries 5 questions

What backup time does the IST3-J offer?

The 1–3 kVA standard models give 3 minutes at full load with internal batteries, extended with BBJ (2U, up to 8 × 12 V 9 Ah) or BBJ2 (3U, up to 16 × 12 V 9 Ah) rack cabinets. The 6 and 10 kVA are long backup models with no internal batteries: an external string of 192 V by default (12–20 × 12 V settable) sets the backup time, with 1 to 8 BBJ2 cabinets.

Answered on IST3-J

IST3-J: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

ModelFull loadBackup at full loadAt half loadFor exampleIts backup
IST3-J 1 kVA1 kW4 to 53 minutes15 to 131 minutes3 × 12 V 9 Ah (IST3J-1-3X9)4 min at 100%, 15 at 50%
IST3-J 2 kVA2 kW2 to 41 minutes8 to 101 minutes4 × 12 V 9 Ah (IST3J-2-4X9)2 min at 100%, 8 at 50%
IST3-J 3 kVA3 kW2 to 30 minutes8 to 78 minutes6 × 12 V 9 Ah (IST3J-3-6X9)2 min at 100%, 8 at 50%
IST3-J 6 kVA6 kW4 to 86 minutes13 to 218 minutes16 × 12 V 9 Ah (IST3J-6-16X9)4 min at 100%, 13 at 50%
IST3-J 10 kVA10 kW2 to 45 minutes5 to 108 minutes16 × 12 V 9 Ah (IST3J-10-16X9)2 min at 100%, 5 at 50%

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

How long does the IST3-J 3 kVA run on battery?

2 minutes at full load and 8 at half load on its six internal 12 V 9 Ah batteries, in AEC's data (the catalogue prints 3 minutes). Battery boxes or BBJ cabinets extend it: the codes IST3J-3-[n]X9 give the total number of 9 Ah blocks, and AEC sizes the number for your load.

Answered on IST3-J 3 kVA

Can the IST3-J 3 kVA batteries be changed with the load on?

Yes: on 1–3 kVA the battery packs of the UPS and of the battery box are hot-pluggable from the front, after removing the plastic panel and the battery plate. Use packs of the same capacity, model and make.

Answered on IST3-J 3 kVA

Does the IST3-J 6 kVA have internal batteries?

No. It is a long backup model (L): the battery is external, 192 V by default, in one to eight BBJ2 rack cabinets of 16 × 12 V 9 Ah each. The backup time is set by the battery you choose.

Answered on IST3-J 6 kVA

Installation, size and connections 8 questions

Can the IST3-J be mounted in a rack and as a tower?

Yes for the 1–3 kVA: every model from 1 to 10 kVA is 19-inch and 2U high, and the 1–3 kVA models can also stand as a tower: the LCD reading is set to RCK (rack, default) or TWR (tower) from the panel. The battery box always mounts below the UPS.

Answered on IST3-J

What do the programmable outlets do?

On 1–3 kVA, the optional programmable outlets switch off non-critical loads after a time limit of 0–999 minutes on battery, set from the PC (default 999). The general outlets keep the critical loads running, so they get more backup time.

Answered on IST3-J

What are the IST3-J dimensions, weights and outlets?

The 1 kVA measures 438 × 423 × 86 mm (14 kg) with 8 × IEC C13 outlets. The 2–3 kVA measure 438 × 572 × 86 mm (20 / 26 kg) with 8 × C13 + 1 × C19; the 6–10 kVA measure 438 × 500 × 86 mm (10.6 / 12.2 kg) with 2 × C13 and a wire terminal. On 1–3 kVA leave at least 300–500 mm around the UPS and 500 mm on top.

Answered on IST3-J

IST3-J: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

ModelSizeWeight
IST3-J 1 kVA438 × 423 × 86 mm14 kg
IST3-J 2 kVA438 × 572 × 86 mm20 kg
IST3-J 3 kVA438 × 572 × 86 mm26 kg
IST3-J 6 kVA1438 × 500 × 86 mm10.6 kg
IST3-J 10 kVA1438 × 500 × 86 mm12.2 kg

Unless marked: size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.

1 Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

Rack or tower: how is the IST3-J 1 kVA installed?

In a 19-inch rack with two angle irons (default reading RCK), or upright on its support bases with the display set to TWR from the panel. With a battery box, two 1U joint bases are added per box.

Answered on IST3-J 1 kVA

How much rack space do the IST3-J 2 kVA and its batteries take?

2U for the UPS (438 × 572 × 86 mm, 20 kg) and 2U for each battery box of the same footprint, which holds 2 × (4 × 12 V 9 Ah) and weighs 29 kg. The catalogue's example rack is the UPS with two battery boxes below it.

Answered on IST3-J 2 kVA

What breaker and cable does the IST3-J 2 kVA need?

12 A maximum input current, a 20 A breaker without leakage protection and a 1.5 mm² AC cable for about 5 m; 6 mm² for the external battery, rated 42.6 A.

Answered on IST3-J 2 kVA

What breaker does the IST3-J 6 kVA need?

The catalogue recommends a 50 A upstream input breaker (36 A maximum input current) and a 50 A DC breaker for the battery, which draws up to 39 A. Size the cables on these currents.

Answered on IST3-J 6 kVA

Communication and monitoring 1 question

Which communication options does the IST3-J have?

RS232 with power management software is standard, plus USB on 1–3 kVA and an EPO input. The intelligent slot takes an optional SNMP card (RJ45 network port and COM1 for a temperature and humidity module), an RS485 and dry-contact card, or a protocol transfer card (1–3 kVA).

Answered on IST3-J

Warranty, service and maintenance 1 question

Can the batteries be replaced without switching off?

Yes, on the 1–3 kVA: the battery packs of the UPS and of the battery box are hot-pluggable and replaced from the front, using the same capacity, model and make. The charging current is 1 A by default, settable to 2–8 A with the 7 A charging module.

Answered on IST3-J

Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.