Questions and answers

IST6 400–1200: questions and answers

22 questions about the AEC IST6 400–1200, from its range page and its 6 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 10 questions

Which cabinet sizes does the IST6 400–1200 kVA come in?

Six cabinets with 4 to 12 power modules of 100 kVA (3U, 54 kg each). The 400, 500, 600 and 800 kVA in a single column of 801 × 1000 × 2000 mm, 1000 and 1200 kVA in a double column of 1201 × 1000 × 2000 mm. With the optional distribution cabinet the 800 kVA is 1400 mm wide and the 1000–1200 kVA 1800 mm.

Answered on IST6 400–1200

What is the difference between General and PLUS power modules?

System efficiency in double conversion is up to 97.2% with General modules and 98.1% with PLUS modules; ECO mode reaches 99.2%. At 800 kW, AEC's indicative calculation shows PLUS modules saving 7.6 kW of losses, about 66,200 kWh per year.

Answered on IST6 400–1200

How far can the system grow in parallel?

Up to eight UPS in parallel, for up to 9.6 MW, with N+X redundancy between UPS and load sharing within 5%. Dual-bus (BSC) and three-bus layouts are supported, and power modules can be added in free slots up to the cabinet rating.

Answered on IST6 400–1200

How much do PLUS modules save on an IST6-1000?

At 800 kW, 8,760 hours a year, losses fall from 23.0 kW (General, 97.2%) to 15.5 kW (PLUS, 98.1%), cooling excluded. The catalogue gives this as an indicative example.

Answered on IST6-1000, 10 × 100 kVA

IST6 400–1200: what is the ordering code of each model?

As the EMEA 2026 catalogue lists them:

AEC gives the full code, batteries included, from the load and the backup time.

Each model's own page, linked in the table, gives its full answer and data.

How many IST6-1200 can work in parallel?

Up to eight, for 9.6 MW, with current imbalance within 5% and N+X redundancy between UPS. Each UPS output is kept within ± 2 V and ± 0.1 Hz of the system setting.

Answered on IST6-1200, 12 × 100 kVA

Does the IST6 400 kVA include the power switches?

Yes: on 400–600 kVA the mains, output, maintenance bypass and bypass switches are inside the cabinet; a version without switches is also available. From 800 kVA the switches move to an optional distribution cabinet.

Answered on IST6-400H, 4 × 100 kVA

Can the IST6 400 kVA stand against a wall?

Yes, with the top air outlet kit, shipped as an accessory for 400–600 kVA: hot air leaves from the top instead of the rear; the top clearance then rises to 650 mm. Without it, keep 500 mm free at the rear.

Answered on IST6-400H, 4 × 100 kVA

How do I make a 500 kVA IST6 redundant?

Fit a sixth 100 kVA module in the free slot of the 500 / 600 kVA cabinet: five carry the load and one is redundant (N+1). Redundancy sleep lets the spare module rest at light load.

Answered on IST6-500H, 5 × 100 kVA

What do PLUS modules change?

Efficiency in double conversion: up to 98.1% with PLUS modules against 97.2% with General modules, same 100 kVA rating and 3U size. ECO mode reaches 99.2% and W-ECO 99%.

Answered on IST6-500H, 5 × 100 kVA

Backup time and batteries 3 questions

Which battery configuration does it use?

Lead-acid: 480 V DC nominal with 40 × 12 V blocks (360–600 V), 30 to 50 blocks accepted with reduced output below 40 blocks, battery neutral optional (±240 V). Lithium: 512 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is 20 A per power module.

Answered on IST6 400–1200

IST6 400–1200: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

ModelFull loadBackup at full loadAt half loadFor exampleIts backup
IST6-600H, 6 × 100 kVA600 kW3 to 52 minutes8 to 104 minutes120 × 12 V 100 Ah · 4 × 30 (IST6-600-120X100)3 min at 100%, 8 at 50%
IST6-800, 8 × 100 kVA800 kW4 to 39 minutes9 to 78 minutes180 × 12 V 100 Ah · 6 × 30 (IST6-800-180X100)4 min at 100%, 9 at 50%
IST6-1000, 10 × 100 kVA1,000 kW3 to 31 minutes7 to 62 minutes180 × 12 V 100 Ah · 6 × 30 (IST6-1000-180X100)3 min at 100%, 7 at 50%
IST6-1200, 12 × 100 kVA1,200 kW3 to 26 minutes8 to 52 minutes240 × 12 V 100 Ah · 8 × 30 (IST6-1200-240X100)3 min at 100%, 8 at 50%

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

What charging current does the IST6 600 kVA give?

20 A per power module, so up to 120 A with six modules, in three stages. The charge limit for lead-acid is 0.05–0.5 C, set on the screen with the battery parameters.

Answered on IST6-600H, 6 × 100 kVA

Installation, size and connections 3 questions

What installation clearances does it need?

At least 800 mm at the front, 500 mm (400–600 kVA) or 800 mm (800–1200 kVA) at the rear and 500 mm on top (650 mm with the top air outlet kit on 400–600 kVA). It runs without derating up to 40 °C, up to 2000 m, with top cable entry as standard and bottom entry via the side wiring cabinet; it is not for open installations within 3.7 km of the sea.

Answered on IST6 400–1200

IST6 400–1200: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

ModelSizeWeight
IST6-400H, 4 × 100 kVA801 × 1000 × 2000 mm345 kg without modules
IST6-500H, 5 × 100 kVA801 × 1000 × 2000 mm434 kg without modules
IST6-600H, 6 × 100 kVA801 × 1000 × 2000 mm434 kg without modules
IST6-800, 8 × 100 kVA801 × 1000 × 2000 mm435 kg without modules
IST6-1000, 10 × 100 kVA1201 × 1000 × 2000 mm662 kg without modules
IST6-1200, 12 × 100 kVA1201 × 1000 × 2000 mm662 kg without modules

Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

Where do the cables enter the IST6 600 kVA?

From the top as standard; bottom entry needs the side wiring cabinet (trench 750 × 300 × 120 mm). The cabinet is fixed with M12 expansion bolts to the floor or a C-steel base.

Answered on IST6-600H, 6 × 100 kVA

Communication and monitoring 1 question

Which communication options does it offer?

Modbus (address 1–247, 2400–19200 baud), RS232 for an external SNMP card, RS485, EPO1 / EPO2 and 4 dry-contact inputs / 3 outputs are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion and a BMS card for lithium batteries.

Answered on IST6 400–1200

Efficiency and operation 2 questions

What noise and environment does the IST6-1200 need?

Below 80 dB at 1 m from the front; 0–40 °C without derating, 0–95% humidity, up to 2000 m, IP20. It is not for open installations within 3.7 km of the sea.

Answered on IST6-1200, 12 × 100 kVA

How does the IST6-800 behave on a generator?

Power walk-in limits the inrush on the mains or generator, and in multi-UPS sites the rectifiers restart in sequence. Smart generator mode starts and stops the generator by dry contact and can take part of the power from the battery.

Answered on IST6-800, 8 × 100 kVA

Warranty, service and maintenance 3 questions

How is service carried out without stopping the load?

All modules are hot-swappable, including the bypass module and the five cards of the system control box, with dual DSP control and two control cards backing each other up. The redundant fans keep a module running at 40% load with one fan failed.

Answered on IST6 400–1200

Is the maintenance bypass included on the IST6-1000?

Not in the distribution cabinet: for 1000 and 1200 kVA it holds mains, bypass and output breakers only. Plan the maintenance bypass in the site switchboard; AEC engineers size the whole system.

Answered on IST6-1000, 10 × 100 kVA

How wide is an IST6-800 with its switchgear?

801 mm for the UPS alone, 1400 mm with the optional distribution cabinet fitted on the left at the factory, which holds the mains, bypass, maintenance bypass and output switches.

Answered on IST6-800, 8 × 100 kVA

Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.