IST7 10–40 · Three-phase UPS
IST7-30 Three-phase UPS 30 kVA, 400 V
The IST7-30 is a 30 kVA / 30 kW online double-conversion UPS in the tall IST7 frame, 300 × 842 × 1250 mm. For data rooms, telecom sites and plants with a three-phase supply and loads of about 20 to 30 kW.
Quick answers
IST7-30: quick answers
- What it is
- The IST7-30 is a 30 kVA / 30 kW online double-conversion UPS in the tall IST7 frame, 300 × 842 × 1250 mm.
- Who it is for
- For data rooms, telecom sites and plants with a three-phase supply and loads of about 20 to 30 kW.
- Supply and configuration
- 3/3 · 3/1 · L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V
- Battery and backup
- ± 144 … ± 240 V DC
- Size and weight
- 300 × 842 × 1250 mm · 102.5 / 249.7 kg
- Ordering code
- IST7-30
IST7 10–40
What sets apart the IST7-30
With the IST7-30 the range moves to the 300 mm frame: 1250 mm high, on castors and levelling feet. The taller cabinet holds two strings of internal batteries: the S model carries 2 × 36 or 2 × 40 blocks of 9 Ah and weighs 249.7 kg, against 102.5 kg for the standard model with external batteries.
From 30 kVA the input must be three-phase: the IST7-30 works 3/3 or 3/1, not 1/1. The output distortion drops to ≤ 1% on resistive load (≤ 2% on 10–20 kVA) and the charger goes up to 20 A (default 2 A), useful with larger external batteries.
- Against the IST7-20 (one size down): Rated power 30 kVA / 30 kW against 20 kVA / 20 kW; Input / output configuration 3/3 · 3/1 against 3/3 · 3/1 · 1/1; Connection 3 + N + PE against 3 + N + PE (settable 1 + N + PE); Charge current (A) 1–20 (default 2) against 1–10 (default 1).
- Against the IST7-40 (one size up): Rated power 30 kVA / 30 kW against 40 kVA / 40 kW.
Planning data
IST7-30: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-30.
Two frames, one family
| Difference | IST7-30 · 40 |
|---|---|
| Ratings · kVA = kW | 30 · 40 |
| Input / output | 3/3 · 3/1 |
| Set on site with | wiring, jumpers, screen, mode connector |
| Cabinet W × D × H | 300 × 842 × 1250 mm |
| Weight standard / S | 102.5 / 249.7 kg |
| Internal batteries (S), 12 V 9 Ah | 2 × 36 or 2 × 40 blocks |
| Battery cells, settable | ±72 … ±120 |
| Charge current | 1–20 A, default 2 A |
| Output distortion, resistive load | ≤ 1% |
| Max. input current, 3/3 | 65.7 A (30) · 81.7 A (40) |
| Max. battery current | 82.2 A (30) · 109.6 A (40) |
| Feet | castors and levelling feet |
Front, rear and footprint
| Model | IST7-30 |
|---|---|
| W × D × H (mm) | 300 × 842 × 1250 |
| Standard | 102.5 kg |
| S | 249.7 kg |
Ready for the site, cables and breakers sized
| Model | IST7-30 |
|---|---|
| AC input (A) | 65.7 |
| AC output (A) | 45.5 |
| Battery (A) | 82.2 |
| Input · output breaker | 100 A 3P |
| Battery breaker | 125 A 3P |
| AC cables (mm²) | 16 |
| Battery (mm²) | 2 × 10 |
| PE (mm²) | 16 |
Single-phase output · 3/1 and 1/1
| Model | IST7-30 |
|---|---|
| AC input (A) (3/1) | 65.7 |
| Bypass input (A) | 197.1 |
| AC output (A) | 136.4 |
| Bypass · output breaker | 250 A 1P · 200 A 1P |
| N, bypass, output (mm²) | 2 × 25 |
| PE (mm²) | 25 |
BB5 to BB8, matched to every IST7
| UPS | IST7-30 · 40 |
|---|---|
| BB5 | 36–40 × 24 Ah · 30–38 × 40 Ah |
| BB6 | 30–36 × 60 Ah |
| BB7 | 30–36 × 80 / 100 Ah |
| BB8 | 40 / 60 × 80 / 100 Ah |
One code for the UPS and its batteries
| Battery | Cabinet | IST7-30 |
|---|---|---|
| Internal 9 Ah · S | — | 72 · 80 (2 strings) |
| Internal 9 Ah + BB5 | BB5 | 200 |
| 24 Ah | BB5 | 36 · 38 · 40 |
| 40 Ah | BB5 | 30* · 32 – 38 |
| 60 Ah | BB6 | 30* · 32 – 36 |
| 80 Ah · 100 Ah | BB7 | 30* · 32 – 36 |
| 80 Ah · 100 Ah | BB8 | 40 · 60* |
Installation
Installing the IST7-30: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not given | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Cable entry | Rear terminals, cables tied down to the bottom | AEC IST7 10–40 user manual |
| Heat at full load | 1.25 kW at 30 kW load, 96 % efficiency | AEC IST7 10–40 user manual p.83 §A; output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | −5 to 40 °C, best 20–25 °C | AEC IST7 10–40 user manual p.6 §1.3 |
| Switches and terminals | Input, bypass, battery, output and maintenance bypass breakers on the rear panel; terminals behind the wiring cover. No front door. | AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3 |
| Units in parallel | Up to 4 units | AEC IST7 10–40 user manual p.71 §4.5.7 |
Size and floor
How big it is
300 × 842 × 1250 mm · 102.5 / 249.7 kg.
Floor load = weight ÷ footprint: 406 kg/m² at the lowest weight given (102.5 kg), 989 kg/m² at the highest (249.7 kg).
Efficiency
How efficient is the AEC IST7-30 at your load?
IST7-30, 30 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.36 kW (η 95.4%) · 50%: 0.63 kW (η 96%) · 75%: 1.01 kW (η 95.7%) · 100%: 1.45 kW (η 95.4%). At 50% load, 24/7, it loses about 5,475 kWh a year.
How the curve is drawn and where each figure comes from: the IST7 10–40 range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | all |
EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.
Drag to turnIn 3D
Look around the IST7-30
The turntable shows the IST7-40; the full 3D view opens on the IST7-30.
Technical data
Technical data IST7-30
Only this model's values, from the EMEA 2026 catalogue table.
| General | |
|---|---|
| Rated power (kVA / kW) | 30 / 30 |
| Input / output configuration | 3/3 · 3/1 |
| Input | |
| Connection | 3 + N + PE |
| Voltage range | 176–280 V at 100% load · 80–176 V with linear derating |
| Frequency range | 39.5–70.5 Hz |
| Bypass synchronisation range · bypass voltage range | 50 / 60 Hz ± 10% (self-adapting) · 10 / 15 / 20% (default 20%) |
| Power factor · THDi | ≥ 0.99 · ≤ 3% resistive full load, ≤ 5% non-linear full load |
| Battery | |
| Battery voltage (Vdc) | ± 144 … ± 240 |
| Cells (2 V), settable · default | ± 72 … ± 120 · ± 96 |
| Charge current (A) | 1–20 (default 2) |
| Output | |
| Connection | 3 + N + PE |
| Voltage | L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V |
| Frequency | tracks the bypass; with bypass absent or out of range 50 ± 0.1 or 60 ± 0.1 Hz (default 50) |
| Waveform · power factor | sine wave · 1 (settable 0.9) |
| Voltage distortion (resistive / non-linear) | ≤ 1% / ≤ 4% |
| Transfer time inverter ↔ bypass | < 1 ms synchronised · < 10 ms not synchronised |
| Inverter overload (PF 1) | < 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · 155–200% 200 ms · > 200% immediate |
| Bypass overload | < 130% continuous · 130–155% 1 min · > 155% 200 ms |
| System | |
| System efficiency | up to 96% · 99% in ECO mode (single UPS) |
| Parallel | up to 4 units with the optional parallel kit |
| Display · communication | touch screen · RS485 · dry contacts: EPO, 1 input, 5 outputs · optional cards: SNMP, protocol transfer, dry-contact kit |
| DC start · alarms | battery start fitted · battery low voltage, mains abnormal, UPS fault, output overload |
| Environment | −5 … 40 °C · 0–95% RH non-condensing · IP20 · noise < 55 dB (25 °C) · up to 2000 m |
| Dimensions W × D × H | 300 × 842 × 1250 mm |
| Weight standard / S | 102.5 / 249.7 kg |
| Item | IST7-30 |
|---|---|
| Rated power (kVA / kW) | 30 / 30 |
| Input / output | 3/3 · 3/1 |
| W × D × H (mm) | 300 × 842 × 1250 |
| Weight standard | 102.5 kg |
| Weight S | 249.7 kg |
20–40 kVA with ±72 … ±90 cells (24–30 blocks): output 75% of rating. S: with internal battery. Outer dimensions in mm: 10–20 kVA width 250 (308 with feet), depth 756 (806 overall), height 802 (880 overall); 30–40 kVA width 300 (358 with feet), depth 787 (842 overall), height 1143 (1250 overall). Ratings are kVA = kW at output PF 1; PF 0.9 settable. Battery voltage and capacity set on the screen at commissioning. Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST7-30
| Code | Description |
|---|---|
| IST7-10 · IST7-20 · IST7-30 · IST7-40 | Standard models, external batteries only (e.g. IST7-30: 30 kVA, external batteries). |
| Parallel kit | Option: built-in card with parallel cables, CAN communication, up to 4 units. |
| SNMP card | Option: network monitoring in an intelligent slot, configured through its web page. |
| Dry-contact kit | Option: 3 outputs and 2 inputs in an intelligent slot. |
| Protocol transfer card | Option: RS485 + RS232 on DB9; RS485 reserved for lithium battery communication. |
Questions
Questions about the IST7-30
Can the IST7-30 feed single-phase loads?
Yes, in 3/1: three-phase input, single-phase output. The catalogue gives 197.1 A at the bypass input and 136.4 A at the output in 3/1, with 2 × 25 mm² neutral, bypass and output cables. A single-phase input (1/1) is not available on 30 kVA.
How many internal batteries does the IST7-30 S hold?
Two strings: 72 or 80 batteries of 12 V 9 Ah in total. With a BB5 added, the code goes to 200 × 9 Ah. External-only versions use 24 Ah (36–40 blocks) or 40, 60, 80 and 100 Ah batteries in BB5 to BB8.
Which breakers does the IST7-30 need?
In 3/3: 100 A 3P at input and output and a 125 A 3P battery breaker, with 16 mm² AC cables and 2 × 10 mm² battery cables for about 5 m. The maximum battery current is 82.2 A.
How long does a 30 kVA UPS like the IST7-30 run?
4 to 52 minutes at full load (30 kW), and 11 to 224 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 36 × 12 V 24 Ah (IST7-30-36X24): 4 minutes at 100% and 15 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST7-30 and how much does it weigh?
The AEC IST7-30 measures 300 × 842 × 1250 mm; weight: 102.5 / 249.7 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST7-30?
In the EMEA 2026 catalogue the AEC IST7-30 is listed as IST7-30; AEC gives the full code, batteries included, from the load and the backup time.