IST7 10–40 · Three-phase UPS

IST7-40 Three-phase UPS 40 kVA, 400 V

VRLA40 kVAonline UPS, 3/3 · 3/1

The IST7-40 is a 40 kVA / 40 kW online double-conversion UPS, the largest of the IST7 10–40 range, in the 300 × 842 × 1250 mm frame. For data rooms, hospitals' technical rooms and industrial lines of 30 to 40 kW, and for parallel systems of up to four units.

40 kVA / 40 kWRating
300 × 842 × 1250 mmW × D × H
102.5 / 249.7 kgWeight
± 144 … ± 240 V DCBattery

Quick answers

IST7-40: quick answers

What it is
The IST7-40 is a 40 kVA / 40 kW online double-conversion UPS, the largest of the IST7 10–40 range, in the 300 × 842 × 1250 mm frame.
Who it is for
For data rooms, hospitals' technical rooms and industrial lines of 30 to 40 kW, and for parallel systems of up to four units.
Supply and configuration
3/3 · 3/1 · L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V
Battery and backup
± 144 … ± 240 V DC
Size and weight
300 × 842 × 1250 mm · 102.5 / 249.7 kg
Ordering code
IST7-40 · IST7-40-34X60

IST7 10–40

What sets apart the IST7-40

The IST7-40 shares cabinet and weight with the IST7-30 (102.5 kg standard, 249.7 kg S) but draws 81.7 A per phase in 3/3 and up to 109.6 A from the battery, so it takes a 175 A 3P battery breaker. The catalogue's operating-cost example is built on this model: at 80% load (32 kW) and 96% efficiency the losses are 1.33 kW, about 11,680 kWh a year; in ECO mode at 99% they fall to 0.32 kW.

Up to four IST7-40 units run in parallel with the optional kit, for 160 kVA of capacity or N+1 redundancy. A version with an internal transformer (IST7-40 T) is listed at 222 kg.

  • Against the IST7-30 (one size down): Rated power 40 kVA / 40 kW against 30 kVA / 30 kW.

Planning data

IST7-40: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST7-40.

Two frames, one family

IST7-40 · Two frames, one family
DifferenceIST7-30 · 40
Ratings · kVA = kW30 · 40
Input / output3/3 · 3/1
Set on site withwiring, jumpers, screen, mode connector
Cabinet W × D × H300 × 842 × 1250 mm
Weight standard / S102.5 / 249.7 kg
Internal batteries (S), 12 V 9 Ah2 × 36 or 2 × 40 blocks
Battery cells, settable±72 … ±120
Charge current1–20 A, default 2 A
Output distortion, resistive load≤ 1%
Max. input current, 3/365.7 A (30) · 81.7 A (40)
Max. battery current82.2 A (30) · 109.6 A (40)
Feetcastors and levelling feet

Front, rear and footprint

IST7-40 · Front, rear and footprint
ModelIST7-40
W × D × H (mm)300 × 842 × 1250
Standard102.5 kg
S249.7 kg

Ready for the site, cables and breakers sized

IST7-40 · Ready for the site, cables and breakers sized
ModelIST7-40
AC input (A)81.7
AC output (A)60.6
Battery (A)109.6
Input · output breaker100 A 3P
Battery breaker175 A 3P
AC cables (mm²)16
Battery (mm²)2 × 10
PE (mm²)16

Single-phase output · 3/1 and 1/1

IST7-40 · Single-phase output · 3/1 and 1/1
ModelIST7-40
AC input (A) (3/1)81.7
Bypass input (A)245.0
AC output (A)181.8
Bypass · output breaker300 A 1P · 250 A 1P
N, bypass, output (mm²)2 × 25
PE (mm²)25

BB5 to BB8, matched to every IST7

IST7-40 · BB5 to BB8, matched to every IST7
UPSIST7-30 · 40
BB536–40 × 24 Ah · 30–38 × 40 Ah
BB630–36 × 60 Ah
BB730–36 × 80 / 100 Ah
BB840 / 60 × 80 / 100 Ah

One code for the UPS and its batteries

IST7-40 · One code for the UPS and its batteries
BatteryCabinetIST7-40
Internal 9 Ah · S—72 · 80 (2 strings)
Internal 9 Ah + BB5BB5200
24 AhBB536 · 38 · 40
40 AhBB530* · 32 – 38
60 AhBB630* · 32 – 36
80 Ah · 100 AhBB730* · 32 – 36
80 Ah · 100 AhBB840 · 60*

Installation

Installing the IST7-40: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST7-40 · installation
ItemFigureSource
Clearancesrear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500); front and top: not givenAEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3
Cable entryRear terminals, cables tied down to the bottomAEC IST7 10–40 user manual
Heat at full load1.67 kW at 40 kW load, 96 % efficiencyAEC IST7 10–40 user manual p.83 §A; output PF 1 (EMEA 2026 catalogue)
Operating temperature−5 to 40 °C, best 20–25 °CAEC IST7 10–40 user manual p.6 §1.3
Switches and terminalsInput, bypass, battery, output and maintenance bypass breakers on the rear panel; terminals behind the wiring cover. No front door.AEC IST7 10–40 user manual p.24 §3.2.3; p.6 §1.3
Units in parallelUp to 4 unitsAEC IST7 10–40 user manual p.71 §4.5.7

Size and floor

How big it is

300 × 842 × 1250 mm · 102.5 / 249.7 kg.

0.25 m²footprint
406–989 kg/m²floor load
1.25 mheight

Floor load = weight ÷ footprint: 406 kg/m² at the lowest weight given (102.5 kg), 989 kg/m² at the highest (249.7 kg).

1.75 mFrontSide3008421250

Efficiency

How efficient is the AEC IST7-40 at your load?

IST7-40, 40 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.48 kW (η 95.4%) · 50%: 0.83 kW (η 96%) · 75%: 1.35 kW (η 95.7%) · 100%: 1.93 kW (η 95.4%). At 50% load, 24/7, it loses about 7,300 kWh a year.

96%50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

How the curve is drawn and where each figure comes from: the IST7 10–40 range page.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4%Typical curve, derived from the datasheet efficiency of 96% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.

AEC IST7-40, rendered from its 3D modelDrag to turn

In 3D

Look around the IST7-40

Technical data

Technical data IST7-40

Only this model's values, from the EMEA 2026 catalogue table.

IST7-40 · Technical data
General
Rated power (kVA / kW)40 / 40
Input / output configuration3/3 · 3/1
Input
Connection3 + N + PE
Voltage range176–280 V at 100% load · 80–176 V with linear derating
Frequency range39.5–70.5 Hz
Bypass synchronisation range · bypass voltage range50 / 60 Hz ± 10% (self-adapting) · 10 / 15 / 20% (default 20%)
Power factor · THDi≥ 0.99 · ≤ 3% resistive full load, ≤ 5% non-linear full load
Battery
Battery voltage (Vdc)± 144 … ± 240
Cells (2 V), settable · default± 72 … ± 120 · ± 96
Charge current (A)1–20 (default 2)
Output
Connection3 + N + PE
VoltageL-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V
Frequencytracks the bypass; with bypass absent or out of range 50 ± 0.1 or 60 ± 0.1 Hz (default 50)
Waveform · power factorsine wave · 1 (settable 0.9)
Voltage distortion (resistive / non-linear)≤ 1% / ≤ 4%
Transfer time inverter ↔ bypass< 1 ms synchronised · < 10 ms not synchronised
Inverter overload (PF 1)< 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · 155–200% 200 ms · > 200% immediate
Bypass overload< 130% continuous · 130–155% 1 min · > 155% 200 ms
System
System efficiencyup to 96% · 99% in ECO mode (single UPS)
Parallelup to 4 units with the optional parallel kit
Display · communicationtouch screen · RS485 · dry contacts: EPO, 1 input, 5 outputs · optional cards: SNMP, protocol transfer, dry-contact kit
DC start · alarmsbattery start fitted · battery low voltage, mains abnormal, UPS fault, output overload
Environment−5 … 40 °C · 0–95% RH non-condensing · IP20 · noise < 55 dB (25 °C) · up to 2000 m
Dimensions W × D × H300 × 842 × 1250 mm
Weight standard / S102.5 / 249.7 kg
IST7-40 · Models
ItemIST7-40
Rated power (kVA / kW)40 / 40
Input / output3/3 · 3/1
W × D × H (mm)300 × 842 × 1250
Weight standard102.5 kg
Weight S249.7 kg

20–40 kVA with ±72 … ±90 cells (24–30 blocks): output 75% of rating. S: with internal battery. IST7-40 T (internal transformer): 222 kg. Outer dimensions in mm: 10–20 kVA width 250 (308 with feet), depth 756 (806 overall), height 802 (880 overall); 30–40 kVA width 300 (358 with feet), depth 787 (842 overall), height 1143 (1250 overall). Ratings are kVA = kW at output PF 1; PF 0.9 settable. Battery voltage and capacity set on the screen at commissioning. Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST7-40

Ordering codes IST7-40
CodeDescription
IST7-10 · IST7-20 · IST7-30 · IST7-40Standard models, external batteries only (e.g. IST7-30: 30 kVA, external batteries).
IST7-40-34X6040 kVA + BB6, 34 × 60 Ah.
Parallel kitOption: built-in card with parallel cables, CAN communication, up to 4 units.
SNMP cardOption: network monitoring in an intelligent slot, configured through its web page.
Dry-contact kitOption: 3 outputs and 2 inputs in an intelligent slot.
Protocol transfer cardOption: RS485 + RS232 on DB9; RS485 reserved for lithium battery communication.

Questions

Questions about the IST7-40

How much energy does the IST7-40 lose in a year?

At 80% load (32 kW), 8,760 hours a year, the catalogue gives 1.33 kW of losses and 11,680 kWh a year in double conversion at 96%, and 0.32 kW and 2,830 kWh in ECO mode at 99% (single UPS). Cooling is excluded; the values are indicative.

Can four IST7-40 work together?

Yes. With the optional parallel kit (a built-in card with CAN communication and two redundant RJ45 ports) up to four units share the load, in redundant or expand mode. ECO mode is for a single UPS only.

What battery cabinet suits a 40 kVA IST7?

BB5 to BB8: the catalogue lists BB5 with 36–40 × 24 Ah or 30–38 × 40 Ah and BB6 with 30–36 × 60 Ah. It also lists BB7 with 30–36 × 80 / 100 Ah and BB8 with 40 or 60 × 80 / 100 Ah. For example IST7-40-34X60, a BB6 with 34 × 60 Ah. Strings of 30 blocks limit the output to 75%.

How long does a 40 kVA UPS like the IST7-40 run?

3 to 35 minutes at full load (40 kW), and 6 to 152 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 36 × 12 V 24 Ah (IST7-40-36X24): 3 minutes at 100% and 10 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST7-40 and how much does it weigh?

The AEC IST7-40 measures 300 × 842 × 1250 mm; weight: 102.5 / 249.7 kg (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).

What is the ordering code of the AEC IST7-40?

In the EMEA 2026 catalogue the AEC IST7-40 is listed as IST7-40, IST7-40-34X60; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST7-40: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.