Questions and answers

All-in-One: questions and answers

14 questions about the AEC All-in-One, from its range page and its 1 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 5 questions

What backup does the All-in-One 20 kVA give?

At 20 kW: 15, 22, 30, 37, 45, 52 or 60 minutes with two to eight 50 Ah modules, and 60 minutes with four 100 Ah modules. At 6 kW: 50 to 200 minutes with 50 Ah modules, 200 minutes with the 100 Ah version. Reference values, confirmed by AEC for each system.

Answered on All-in-One 20 kVA

Is there a single-phase All-in-One, or one above 20 kVA?

No. The All-in-One is built as 20 kVA only, three-phase input, 3/3 or 3/1: the 3/1 mode feeds single-phase loads. For a single-phase supply look at the IST3, IST3-J or IST8; for lithium above 20 kVA, at the L6 cabinets with the IST7 60–200 kVA or the IST6.

Answered on All-in-One 20 kVA

Can modules be added later?

Yes, with 50 Ah modules, up to eight: each module has its own DC/DC converter, so new modules work beside the ones in service and go in with the load supplied. The 100 Ah version is always four modules.

Answered on All-in-One 20 kVA

What are the ordering codes of the All-in-One 20 kVA?

AIO-20K-2X50 to AIO-20K-8X50 with 2 to 8 modules of 50 Ah, and AIO-20K-4X100 with four modules of 100 Ah. Tell us the load and the backup time: AEC chooses the code.

Answered on All-in-One 20 kVA

Which All-in-One fits my load?

There is one: the All-in-One 20 kVA, with the IST9 20 kVA inside, three-phase input, 3/3 or 3/1, for loads up to 20 kW. Two 50 Ah modules already carry the full 20 kW; more modules, or the 100 Ah version, give longer backup. For a single-phase supply or above 20 kVA, AEC proposes another range.

Answered on All-in-One

Backup time and batteries 2 questions

How long does a 20 kVA UPS like the All-in-One 20 kVA run?

15 to 60 minutes at full load (20 kW), and 30 to 120 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 2 × lithium modules 50 Ah (AIO-20K-2X50): 15 minutes at 100% and 30 at 50%. For other loads and batteries use the backup-time tool.

Answered on All-in-One 20 kVA

What backup time can the All-in-One reach?

Up to 200 minutes at 6 kW with 8 × 50 Ah or 4 × 100 Ah modules. At the full 20 kW the tables give 15 to 60 minutes with 2 to 8 × 50 Ah modules and 60 minutes with 4 × 100 Ah. These are reference values to be confirmed by actual measurement, and AEC sizes every system.

Answered on All-in-One

Lithium batteries 4 questions

Lithium All-in-One or UPS with VRLA batteries?

AEC's comparison in the catalogue: one cabinet instead of UPS plus battery cabinet, installed by one person in 30–60 minutes instead of two people in 2–4 hours. The lithium lasts 10+ years with 5,000 cycles at 50% depth of discharge against 3–5 years and about 500 cycles for VRLA.

Answered on All-in-One 20 kVA

What is inside the All-in-One cabinet?

An IST9 20 kVA online double-conversion rack UPS (three-phase, 3/3 or 3/1), the distribution switches with maintenance bypass and 2 to 8 hot-swappable 50 Ah lithium modules, or four of 100 Ah, factory-built into one 600 × 1000 × 1110 mm cabinet on castors. One touch screen on the door shows UPS and battery down to the cell.

Answered on All-in-One

Which lithium modules should I choose?

The 50 Ah modules (2.88 kWh each, 2 to 8 per cabinet, 10 kW each) are for short and medium backup times; the 100 Ah version (5.76 kWh each, always 4 per cabinet, 5 kW each) is for long backup. Both are lithium iron phosphate and hot-swappable, and a faulty module leaves the system on its own while the others keep supplying the load.

Answered on All-in-One

How long do the lithium modules last compared with lead-acid?

The LFP cells are rated for 5,000 cycles at 50% depth of discharge and 10+ years, against about 500 cycles and 3–5 years for VRLA in AEC's indicative comparison. Each module has its own DC/DC converter, so new modules can be added later and work together with the older ones.

Answered on All-in-One

Installation, size and connections 2 questions

How big is the AEC All-in-One 20 kVA and how much does it weigh?

The AEC All-in-One 20 kVA measures 600 × 1000 × 1110 mm; weight: 232 kg with 2 × 50 Ah, up to 460 kg with 8 × 50 Ah (EMEA 2026 catalogue).

Answered on All-in-One 20 kVA

How long does installation take?

AEC indicates 1 person and 30–60 minutes for the All-in-One, against 2 people and 2–4 hours for a UPS with a separate VRLA cabinet. Only mains, bypass and output are wired on site; the cabinet measures 600 × 1000 × 1110 mm on castors and weighs 232 to 460 kg complete (352 kg with 4 × 100 Ah).

Answered on All-in-One

Communication and monitoring 1 question

How is the All-in-One monitored?

RS485 links UPS, battery BMS and touch screen as standard, and the touch screen exports records and takes firmware upgrades from USB. An SNMP card and a dry-contact card are optional.

Answered on All-in-One

Still a question?

Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.