What is the difference between a standard and a long backup IST3?
Standard models have internal 12 V 9 Ah batteries (2, 4, 6 or 16 depending on the rating); long backup models (-L) have no internal batteries and run on external cabinets at 36, 72, 96 or 192 V. The 1–3 kVA long backup models are the same size as the standard ones, while the 6–10 kVA long backup unit measures 190 × 429 × 337 mm and weighs 11.0 / 12.5 kg.
Answered on IST3
Which IST3 rating do I need for my load?
Compare your load in watts with the rated power: 1000 W (1 kVA), 2000 W (2 kVA), 3000 W (3 kVA), 6000 W (6 kVA) and 10,000 W (10 kVA), at output power factor 1. Do not connect unbalanced, half-wave rectified or inductive loads such as air conditioners, motors, drills or fluorescent lamps.
Answered on IST3
Which input and output voltages does the IST3 accept?
The output is 220 V by default and can be set to 208, 220, 230 or 240 V from the front panel, with no software. On 1–3 kVA the UPS works from the mains, without the battery, from 176 to 295 V at full load and down to 120 V with load below 50%; on 6–10 kVA full load runs from 176 to 275 V, with linear derating down to 80 V.
Answered on IST3
Single-phase 10 kVA: IST3-10 or IST7-10 in 1/1?
Both work single-phase in and out. The IST3-10 is 10 kW (PF 1), 56.2 kg, in a 553 mm high tower; the IST7-10 is 10 kW (PF 1) in a 880 mm cabinet, takes up to 40 internal batteries and can later be rewired 3/3 if the site gets a three-phase supply.
Answered on IST3-10
IST3: what is the ordering code of each model?
As the EMEA 2026 catalogue lists them:
| Model | Catalogue code |
|---|---|
| IST3-1 | IST3-1-2X9, IST3-1-L |
| IST3-2 | IST3-2-4X9, IST3-2-L |
| IST3-3 | IST3-3-6X9, IST3-3-L |
| IST3-6 | IST3-6-16X9, IST3-6-L |
| IST3-10 | IST3-10-16X9, IST3-10-L |
AEC gives the full code, batteries included, from the load and the backup time.
Each model's own page, linked in the table, gives its full answer and data.
Which loads should not go on the IST3-2?
The catalogue excludes unbalanced, half-wave rectified or inductive loads such as air conditioners, motors, drills and fluorescent lamps. IT, network and electronic loads are what it is built for.
Answered on IST3-2
Backup time and batteries 8 questions
What backup time does the IST3 give with its internal batteries?
With the internal 12 V 9 Ah batteries, the 1, 2 and 3 kVA standard models give 3 minutes at full load. The 6 kVA gives 5 minutes at full load and 20 minutes at half load, the 10 kVA 1 and 15 minutes. For longer backup, the long backup models connect to external battery cabinets, which set the backup time.
Answered on IST3
How long do the IST3 batteries last and how should they be looked after?
Typical battery life is 3–5 years, depending on temperature and use. Charge for 10 hours before first use, then discharge and recharge every 4–6 months (every 2 months in hot areas); in storage, recharge for more than 10 hours every 3 months.
Answered on IST3
Why is the IST3-10's internal battery so short at full load?
Its internal battery is the same 16 × 12 V 9 Ah as the IST3-6, now carrying 10 kW: 2 minutes at full load and 5 at half load in AEC's data (the catalogue prints 1 and 15). For more backup, the catalogue offers BB3 (up to 32 × 9 Ah, several per UPS) and BB5 (100 × 9 Ah for the IST3 10 kVA).
Answered on IST3-10
IST3: how long does each model run on battery?
Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):
| Model | Full load | Backup at full load | At half load | For example | Its backup |
|---|---|---|---|---|---|
| IST3-1 | 1 kW | 2 to 41 minutes | 8 to 101 minutes | 2 × 12 V 9 Ah (IST3-1-2X9) | 2 min at 100%, 8 at 50% |
| IST3-2 | 2 kW | 2 to 41 minutes | 8 to 101 minutes | 4 × 12 V 9 Ah (IST3-2-4X9) | 2 min at 100%, 8 at 50% |
| IST3-3 | 3 kW | 2 to 86 minutes | 8 to 218 minutes | 6 × 12 V 9 Ah (IST3-3-6X9) | 2 min at 100%, 8 at 50% |
| IST3-6 | 6 kW | 4 to 47 minutes | 13 to 113 minutes | 16 × 12 V 9 Ah (IST3-6-16X9) | 4 min at 100%, 13 at 50% |
| IST3-10 | 10 kW | 2 to 41 minutes | 5 to 101 minutes | 16 × 12 V 9 Ah (IST3-10-16X9) | 2 min at 100%, 5 at 50% |
For other loads and batteries use the backup-time tool.
Each model's own page, linked in the table, gives its full answer and data.
How long does the IST3-1 run on battery?
2 minutes at full load (1000 W) and 8 at half load with its two internal 12 V 9 Ah batteries, in AEC's data (the catalogue prints 3 minutes). For longer backup, a BB1 tower cabinet takes up to 6 × 12 V 9 Ah (code IST3-1-6X9), or the long backup model IST3-1-L runs on an external 36 V battery.
Answered on IST3-1
Can I add batteries to the IST3-2?
Yes. The BB2 tower cabinet, same colour and front as the UPS, holds up to 12 × 12 V 9 Ah (code IST3-2-12X9). The long backup model IST3-2-L (9.0 kg) has no internal batteries and connects to a 72 V external string.
Answered on IST3-2
How do I get a longer backup from the IST3-3?
Add a BB2 cabinet with up to 12 × 12 V 9 Ah (code IST3-3-12X9: 8 minutes at full load and 24 at half load in AEC's data), or choose the long backup model IST3-3-L with an external 96 V battery. The backup then depends on the battery chosen; AEC sizes it on your load.
Answered on IST3-3
How long does the IST3-6 run on its internal batteries?
4 minutes at full load and 13 at half load with 16 × 12 V 9 Ah (192 V), in AEC's data (the catalogue prints 5 and 20). A BB3 tower cabinet adds up to 32 × 12 V 9 Ah, and more than one BB3 can be connected for longer backup.
Answered on IST3-6
Installation, size and connections 5 questions
What are the IST3 dimensions and installation clearances?
Standard models measure 145 × 357 × 226 mm (1 kVA, 8.5 kg), 190 × 397 × 330 mm (2–3 kVA, 17.6 / 22.5 kg) and 230 × 524 × 553 mm (6–10 kVA, 54.5 / 56.2 kg, on wheels with a maintenance bypass switch). Leave at least 300–500 mm free at the rear and sides, on a flat floor tilted less than 5°, at −5 … 40 °C and up to 1000 m without derating.
Answered on IST3
IST3: how big is each model and how much does it weigh?
Width × depth × height and weight, model by model:
| Model | Size | Weight |
|---|---|---|
| IST3-1 | 145 × 357 × 226 mm | 8.5 / 4.6 kg |
| IST3-2 | 190 × 397 × 330 mm | 17.6 / 9.0 kg |
| IST3-3 | 190 × 397 × 330 mm | 22.5 / 9.2 kg |
| IST3-6 | 230 × 524 × 553 mm | 54.5 / 11.0 kg |
| IST3-10 | 230 × 524 × 553 mm | 56.2 / 12.5 kg |
Size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.
Each model's own page, linked in the table, gives its full answer and data.
What breaker does the IST3-1 need upstream?
The catalogue gives 6 A maximum AC input current and a 10 A breaker, without leakage protection, on a 1.5 mm² cable for about 5 m. The long backup model draws up to 37 A from its battery, on a 50 A DC breaker and 6 mm² cable.
Answered on IST3-1
Does the IST3-3 plug into a normal socket?
Not without a check: it has an input socket, but the catalogue gives an 18 A maximum input current with a 32 A breaker and 4 mm² cable. Have an electrician check that the circuit carries it.
Answered on IST3-3
What does the IST3-6 need on the supply side?
A single-phase L + N + PE supply with a 50 A breaker (36 A maximum input current) and a 6 mm² cable for about 5 m, earth cable of the same section. The long backup model draws up to 39 A from the battery on a 50 A DC breaker.
Answered on IST3-6
Communication and monitoring 1 question
Can the IST3 be monitored over the network with SNMP?
Yes: RS232 and USB are standard on every model, and the intelligent slot takes an optional SNMP card or an RS485 and dry-contact card with three contacts (mains abnormal, battery under-voltage, UPS failure). An EPO input is also standard.
Answered on IST3
By range
Still a question?
Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.