Questions and answers

UPS questions answered in the AEC guides

174 questions answered in the blog and the technology articles, grouped by subject. Each answer is the one printed in its guide; the guide has the worked example, the tables and the sources.

Choosing, sizing and ordering 45 questions

How do I size a CPSS?

Add up the power of all safety loads, add a margin for future circuits and pick a CPSS whose output in watts covers the total. Then size the battery for the required duration, including conversion losses and an ageing factor for end of life.

Answered on CPSS to EN 50171: what it asks and how to size one

When do I need a three-phase UPS?

When the load is too large for a single-phase supply, roughly above 20 kVA, or when the site already distributes power on three phases. Factories, hospitals and medium to large data centres usually need three-phase.

Answered on How to choose a UPS: type, runtime, phases and service

Why does a UPS datasheet give both kVA and kW?

kVA is apparent power and kW is real power, linked by the power factor: kW = kVA × PF. A load can exceed one rating while staying within the other. The AEC IST7 10–40 has output PF 1, so its kVA and kW ratings are equal, for example 20 / 20.

Answered on UPS datasheet explained: every line, with examples

What is the difference between kVA and kW?

kVA is apparent power, voltage multiplied by current. kW is active power, the part that does useful work. They are linked by the power factor: kW = kVA × PF, so kW is never higher than kVA.

Answered on kVA vs kW: power factor and UPS sizing explained

How do I convert kVA to kW?

Multiply the kVA by the power factor. At PF 0.8, 10 kVA is 8 kW; at PF 0.9 it is 9 kW; at PF 1 it is 10 kW. To go from kW to kVA, divide by the power factor instead.

Answered on kVA vs kW: power factor and UPS sizing explained

What is the power factor of a UPS?

The output power factor of a UPS tells you how many kW it can deliver per kVA of rating. Common values are 0.8, 0.9 and 1.0. A UPS with output PF 1 delivers its full kVA rating as kW.

Answered on kVA vs kW: power factor and UPS sizing explained

What size UPS do I need for 3 kW?

A 5 or 6 kVA UPS: a 3 kVA unit is too small. At a load PF of 0.9, 3 kW is 3.33 kVA; keeping the load within 80% of the rating means at least 3.75 kW and 4.17 kVA.

Answered on kVA vs kW: power factor and UPS sizing explained

Is a 10 kVA UPS the same as 10 kW?

Only if its output power factor is 1. At output PF 0.9 a 10 kVA UPS delivers 9 kW, and at 0.8 it delivers 8 kW. Read both the kVA and kW ratings on the data sheet.

Answered on kVA vs kW: power factor and UPS sizing explained

What is crest factor in a UPS?

Crest factor is the ratio between peak current and RMS current. A pure sine wave has about 1.41, while IT power supplies without power factor correction can reach around 3. The UPS must supply these peaks without its output voltage collapsing.

Answered on kVA vs kW: power factor and UPS sizing explained

How many L6 modules does a 200 kW UPS need?

From 20 to 43, by backup time: AEC's L6 tables give 20 modules of 40 Ah in one cabinet for 10 minutes and 22 modules of 50 Ah in two cabinets for 15 minutes. For 20 minutes they give 40 modules of 40 Ah, for 30 minutes 43 modules of 50 Ah in three cabinets.

Answered on L6 lithium battery sizing: modules, cabinets, room

Which L6 module should I choose?

By backup time: 40 Ah modules (6C cells) for 10–20 minutes, 50 Ah modules (4C) for 15–30 minutes, 100 Ah modules (1C) for one to four hours. A 100 Ah cabinet delivers 60 kW, so it suits small loads for hours.

Answered on L6 lithium battery sizing: modules, cabinets, room

Can I add L6 modules later?

Yes. Modules are added online and old and new modules work together, each on its own DC/DC converter. A cabinet takes 20 modules of 40 or 50 Ah or 12 of 100 Ah, and up to 15 cabinets work in parallel.

Answered on L6 lithium battery sizing: modules, cabinets, room

What is a modular UPS?

A modular UPS is a cabinet holding several identical power modules, each a complete online double-conversion UPS. The modules share the load, and you add modules as the load grows. One extra module gives N+1 redundancy in the same cabinet.

Answered on Modular UPS: how to grow power module by module

What is a 30 kVA modular UPS?

It usually means a modular system built from 30 kVA power modules. The AEC IST6 30–120 kVA starts with one 30 kVA / 30 kW module and grows to 120 kVA in the same cabinet, with a fifth slot for a redundant module.

Answered on Modular UPS: how to grow power module by module

When is a conventional UPS a better choice than a modular one?

When the load is stable and will not grow, a conventional online UPS is often simpler. For loads from 10 to 200 kVA, ranges such as the IST7 can still run several units in parallel for redundancy.

Answered on Modular UPS: how to grow power module by module

What is a single-phase UPS used for?

A single-phase UPS protects equipment fed from one 230 V phase: PCs, servers, network racks, tills and small server rooms. AEC's single-phase ranges cover 1 to 10 kVA. Above about 20 kVA a three-phase UPS is usually the better choice.

Answered on Single- or three-phase UPS: which does your site need?

Can a three-phase UPS supply single-phase loads?

Yes. Use a 3/1 configuration, which delivers one single-phase output, or a 3/3 UPS with the single-phase loads spread evenly across the three phases. In 3/1 mode the output and neutral cables must be sized for up to three times the phase current.

Answered on Single- or three-phase UPS: which does your site need?

When should I move from single-phase to three-phase?

Usually somewhere between 10 and 20 kVA. Above that, single-phase currents get high and cables and breakers get large. Three-phase loads such as motors need a three-phase UPS whatever the size.

Answered on Single- or three-phase UPS: which does your site need?

What is the difference between a 3/3 and a 3/1 UPS?

A 3/3 UPS takes three phases in and delivers three phases out, for three-phase boards and machines. A 3/1 UPS takes three phases in and delivers one single-phase output, so single-phase loads need no phase balancing. On 3/1 the output cabling must carry the full single-phase current.

Answered on Three-phase UPS: configurations, sizing and installation

How do I calculate the size of a three-phase UPS?

Multiply √3 × line voltage × average phase current to get VA, then multiply by the power factor to get W. For example, √3 × 400 V × 38.3 A is about 26.5 kVA. Also check that the busiest phase stays within a third of the UPS rating, and add a margin of about 20-25%.

Answered on Three-phase UPS: configurations, sizing and installation

What is the difference between a UPS and an inverter?

An online UPS runs the load on its inverter all the time, so there is no break when the mains fails and the output is a clean sine wave. Many home inverter and battery systems switch over when the mains fails, so depending on the design there can be a short break. Check the transfer time before connecting IT equipment.

Answered on UPS vs generator: how they differ and work together

Which UPS is best for frequent power outages?

An online double-conversion UPS with a wide input window, so brownouts do not drain the battery. Add automatic shutdown and, if the cuts are long, a model that takes external battery cabinets.

Answered on UPS for blackouts and storms: what to know

What size UPS do I need for an NVR and a PoE switch?

Add the NVR's power to the switch's own consumption and the real draw of the cameras it feeds, then add about 20%. In this guide's example, 16 cameras, an NVR, a router and a monitor come to about 240 W with margin, which a 1 kVA online UPS covers easily. The runtime you want then decides the battery.

Answered on UPS for CCTV and video surveillance systems

What is the difference between N+1 and 2N?

N+1 adds one spare unit or module to the same system. 2N uses two completely independent systems, each able to carry the whole load, on separate power paths. 2N only protects fully when the IT equipment has dual power supplies.

Answered on UPS for data centres: how to choose and plan

Is a modular UPS better for a data centre?

Yes, for data centres whose load will grow and that need redundancy and service without shutdown. For a stable, smaller load, a conventional online UPS can be enough, and several units can still run in parallel.

Answered on UPS for data centres: how to choose and plan

What size UPS do I need for a home PC and router?

Add up the watts, divide by 0.7 and add about 25% margin. A PC, monitor and router drawing 300 W need about 430 VA before the margin and about 540 VA after it, so a 1 kVA UPS is the realistic choice.

Answered on UPS for home: protect devices, router and data

What transfer time is acceptable for medical loads?

For privileged loads the usual target is no break at all. That is why online double-conversion UPS, where the load always runs from the inverter, are used. IEC 60364-7-710 also sets maximum changeover times for the safety supply, down to 0.5 s or less for a few critical circuits.

Answered on UPS for hospitals and healthcare facilities

Which UPS type is best for industrial applications?

Online double conversion, classed VFI under IEC 62040-3, is the usual choice. In normal operation the load is fed by the inverter, so dips, surges and frequency changes on the mains do not reach it. Add an isolation transformer where the site needs galvanic separation.

Answered on Industrial UPS: protecting PLCs, motors and processes

Which suits manufacturing, a 3/1 or a 3/3 UPS?

Choose 3/3 if any protected load is three-phase, such as motors or drives. Choose 3/1 if all protected loads are single-phase, such as PLC supplies and control panels. Some AEC ranges, such as the IST7 10-40 kVA and IST9, can be set to either.

Answered on Industrial UPS: protecting PLCs, motors and processes

What is the difference between kVA and kW on a UPS?

kVA is apparent power and kW is real power; kW = kVA × power factor. A 10 kVA UPS with PF 0.9 delivers 9 kW, while one with PF 1 delivers 10 kW. Check the load against both ratings.

Answered on UPS glossary: 87 UPS terms and acronyms explained

How far behind an IST7 10–40 kVA must the wall be?

The manual asks for at least 300 mm, 300–500 mm recommended for ventilation. Its breakers and terminals are on the rear panel, so where someone works there, plan the 700 mm operating gangway of HD 60364-7-729.

Answered on UPS installation clearances: what to check on site

What does N+1 UPS mean?

N is the number of UPS units or power modules needed to carry the load, and N+1 adds one spare. If any one unit or module fails or is switched off for service, the others carry the load on inverter. It only works while the load stays within the capacity of N units.

Answered on UPS redundancy: N+1 or 2N, and how much a site needs

What is the difference between N+1 and 2N UPS redundancy?

N+1 adds one spare unit or module inside a single system that feeds the load. 2N builds two complete, independent systems, each able to carry the full load, usually feeding dual-corded equipment. 2N also covers a fault in a whole path, such as a switchboard or cable, but needs about twice the equipment.

Answered on UPS redundancy: N+1 or 2N, and how much a site needs

Is a modular UPS the same as a parallel UPS?

No: both share the load between several power stages, but they are built differently. A parallel UPS system links several complete UPS units on a common load bus. A modular UPS puts several hot-swap power modules in one cabinet, so the spare is a module rather than a whole UPS.

Answered on UPS redundancy: N+1 or 2N, and how much a site needs

How do I size a UPS?

List every device, add up its power in watts and in VA, and choose a UPS that keeps both totals within about 80% of its ratings. Then choose the backup time, which sets the battery. On three-phase systems, also check the load on each phase.

Answered on UPS sizing: how to work out the power you need

Why divide watts by 0.7?

It is a cautious estimate of the power factor when you do not know it. It gives a VA figure that will not leave the UPS undersized. If the UPS has an output power factor of 1, you can also compare watts directly with its kW rating.

Answered on UPS sizing: how to work out the power you need

What size UPS do I need for 1,000 W?

Allow 20% headroom: 1,000 W ÷ 0.8 = 1,250 W. On a UPS with power factor 0.9 that needs at least about 1.4 kVA, so a 2 kVA model; on a UPS with power factor 1, a 2 kVA model also leaves room. Check the VA total of the loads as well.

Answered on UPS sizing: how to work out the power you need

Should I size the UPS for future growth?

Yes, with a margin of about 20% for inrush and a few extra devices. If you expect large growth, look at a modular UPS such as the IST6, which grows in 30 kVA steps in the same cabinet.

Answered on UPS sizing: how to work out the power you need

Is there a UPS size calculator?

Yes: AEC's online UPS finder and backup time calculator apply the sums for you, and AEC engineers size larger systems from your load list. The sums are simple: VA = V × A, VA = W ÷ PF, and minimum rating = total load ÷ 0.8.

Answered on UPS sizing: how to work out the power you need

Which type of UPS power supply do I need for a server?

For servers and network equipment, choose an online double conversion UPS, class VFI, with a sine wave output. Server power supplies expect a clean, uninterrupted supply. Then size the power with a margin and check the runtime you need.

Answered on Online UPS vs line-interactive vs offline: UPS types

What is the difference between a UPS and a CPSS?

A UPS keeps equipment and data running through power cuts, and follows IEC / EN 62040. A CPSS supplies safety systems such as emergency lighting so people can leave a building safely, and follows EN 50171. They share components but are not interchangeable.

Answered on UPS vs CPSS: which one does a building need?

Which buildings need a CPSS?

Typically workplaces and places where many people gather, such as shopping centres, hospitals, museums and schools. The fire safety design and national rules decide whether a central system is needed and for how long it must run.

Answered on UPS vs CPSS: which one does a building need?

What is the difference between a UPS and a surge protector?

A surge protector only clamps voltage spikes and does nothing during a power cut. A UPS contains a battery and an inverter, so it keeps the load running when the mains fails and, if it is online, also cleans up the supply.

Answered on What is a UPS and what does it do?

How do I compare an AEC UPS with the Code's thresholds?

Take your range's row in the table and the values for the UPS's power band and class in the Code's tables published by the JRC. Measured curves are AEC data; derived curves are typical curves, to confirm with AEC for a specification.

Answered on EU Code of Conduct on UPS energy efficiency

What is the difference between an IGBT and a MOSFET?

Both are driven by a voltage on the gate. A MOSFET conducts like a resistor and switches faster, but its resistance rises steeply with the voltage it blocks; an IGBT conducts like a bipolar transistor, with low losses at high voltage and current, which is why it is the switch of a three-phase UPS's power stages.

Answered on From thyristor to silicon carbide

Backup time and batteries 26 questions

What does CPSS stand for?

CPSS stands for central power supply system. It supplies safety equipment such as emergency lighting and smoke extraction from a central battery when the normal supply fails.

Answered on CPSS to EN 50171: what it asks and how to size one

How long must emergency lighting run on a CPSS?

Usually 1 or 3 hours: the duration is set by national rules and the fire safety design of the building, not by the CPSS itself. The battery must deliver that duration at the end of its life.

Answered on CPSS to EN 50171: what it asks and how to size one

How many minutes of backup should I plan for?

For most IT loads, 5 to 10 minutes is enough for a controlled shutdown. Plan for more only when the process cannot stop or a generator must take over, and choose a model that takes external batteries.

Answered on How to choose a UPS: type, runtime, phases and service

Does a UPS datasheet show the backup time?

No, usually not as a single figure, because backup time depends on the battery you fit and the load. The datasheet gives the battery voltage, number of cells and charge current. You then work out runtime from the battery capacity and the load, or ask for a calculation.

Answered on UPS datasheet explained: every line, with examples

Why does my UPS switch to battery when running on a generator?

Usually because the generator voltage or frequency moves outside the UPS input window, often during load steps, or because harmonics distort the generator voltage. An online UPS with a wide input frequency range and low THDi reduces this. A larger or better-regulated generator may also be needed.

Answered on UPS vs generator: how they differ and work together

How much UPS battery runtime do I need with a generator?

Minutes rather than hours, often 5 to 15 as a first figure: enough to cover the generator start and transfer, plus a margin for a failed first start or a manual start. That is much shorter than the runtime needed without a generator. Use a backup time calculator to match the battery to your load.

Answered on UPS vs generator: how they differ and work together

How do I calculate UPS backup time?

For a first estimate, multiply the battery energy in Wh (blocks × 12 V × Ah) by the inverter efficiency and divide by the load in watts. The result is in hours and is optimistic for short, high-power discharges. Confirm it with constant-power runtime tables.

Answered on UPS backup time: how to estimate and extend runtime

Why does halving the load more than double UPS runtime?

Batteries, and lead-acid in particular, deliver fewer usable ampere-hours at high discharge rates. This is often called the Peukert effect. A lighter load lets the battery give more of its stored energy before reaching the end voltage.

Answered on UPS backup time: how to estimate and extend runtime

Does a bigger UPS give more backup time?

Not by itself. Runtime depends on battery energy relative to the load. To get more runtime, add battery cabinets, more lithium modules or a second string, rather than a larger UPS.

Answered on UPS backup time: how to estimate and extend runtime

How much UPS runtime do I need with a generator?

About 5 to 15 minutes as a starting point: enough to bridge until the generator starts and takes the load, plus a margin for a failed start. Your own risk assessment sets the final figure.

Answered on UPS backup time: how to estimate and extend runtime

Does UPS runtime fall as the batteries age?

Yes. Battery capacity falls with age, and faster at high temperature. Size the battery with a reserve so the runtime you need still holds near the end of the battery's life, and test it periodically.

Answered on UPS backup time: how to estimate and extend runtime

How long does a UPS battery last?

VRLA AGM batteries typically last 3-5 years in service, even when their design life is 10-12 years at 20-25 °C. Heat is the main reason: as a rule, life halves for about every 8 °C above 25 °C. LiFePO4 batteries generally last considerably longer.

Answered on UPS batteries: VRLA vs lithium and how to choose

What does 12 V 9 Ah mean on a UPS battery?

It is a 12-volt lead-acid block with a capacity of 9 ampere-hours measured over a 20-hour discharge (C20). At the faster discharge rates of a UPS, the usable capacity is much lower, so runtime is calculated from constant power tables rather than from Ah alone.

Answered on UPS batteries: VRLA vs lithium and how to choose

Can I replace only one battery in a UPS string?

No, not with lead-acid VRLA. The weakest block limits the whole string and mismatched blocks charge unevenly, so replace the full string with the same model, capacity and batch. Modular lithium systems such as AEC's L6 are designed to mix old and new modules.

Answered on UPS batteries: VRLA vs lithium and how to choose

What is a UPS battery cabinet?

A battery cabinet is an enclosure that holds extra UPS batteries beside or under the UPS to extend runtime. It contains the battery string, a DC disconnect with protection and the wiring to the UPS, and it needs ventilation and floor space suited to its weight.

Answered on UPS batteries: VRLA vs lithium and how to choose

How often should UPS batteries be checked?

Check VRLA batteries visually every month and measure the voltage of every block on float about every 6 months. A capacity test or replacement is typical every 3–5 years. Remote monitoring adds continuous checks between visits.

Answered on UPS maintenance: batteries, checks and schedule

How long do UPS batteries last?

6 to 12 years at 25 °C, by block size: OZ Power 9 and 24 Ah blocks have a 6–8 year design life and 40–200 Ah blocks 12 years, in float service. Life halves about every 8 °C above 25 °C, so warm rooms shorten it a lot.

Answered on UPS maintenance: batteries, checks and schedule

Can I replace only one faulty battery block?

No, it is usually better to replace the whole string, so that blocks of different age do not work together. Use the same model, capacity and batch across the string. A technician can advise based on the measurements.

Answered on UPS maintenance: batteries, checks and schedule

How long will a UPS last in a power cut?

About 13 minutes at half load for an IST3 6 kVA, and 2 minutes at full load for the standard IST3 1–3 kVA (AEC data), much longer at light load. For longer runtimes, add battery cabinets or a generator.

Answered on UPS for blackouts and storms: what to know

How long should a CCTV UPS run?

There is no single figure: cover the outages you expect on site, or bridge to a generator with a margin (5 to 15 minutes is a common starting point). At minimum, the NVR must have time to shut down cleanly. If you need more than a few minutes, choose a UPS that accepts external batteries.

Answered on UPS for CCTV and video surveillance systems

What does the UPS acronym stand for?

UPS stands for uninterruptible power supply. It is a device that keeps equipment running from a battery when the mains fails, and filters disturbances while the mains is present.

Answered on UPS glossary: 87 UPS terms and acronyms explained

Do redundant UPS units need separate batteries?

Not necessarily. A common battery saves space and maintenance, but it becomes a shared element that can affect every unit at once. Separate strings keep a battery fault limited to one unit. In both cases, size the runtime for N units, because the spare may be out when the mains fails.

Answered on UPS redundancy: N+1 or 2N, and how much a site needs

Does a larger UPS give more runtime?

Only partly. Runtime depends mainly on the battery capacity compared with the load. To extend it, add external batteries rather than simply buying a bigger UPS.

Answered on UPS sizing: how to work out the power you need

Why is a CPSS battery usually larger than a UPS battery?

A CPSS must supply the safety load for the full required duration, often 1 or 3 hours, at the end of battery life. A UPS often only needs minutes, for example to bridge until a generator starts.

Answered on UPS vs CPSS: which one does a building need?

What does UPS stand for?

UPS stands for uninterruptible power supply. It keeps equipment running from a battery when the mains fails and filters out disturbances while the mains is present. In Italian it is called a gruppo di continuità.

Answered on What is a UPS and what does it do?

What does a 3-level inverter change?

Each switch blocks half the DC bus voltage and the output has three levels instead of two: lower switching losses, half the ripple and a smaller filter. Double conversion goes from the typical 93–95% of 2-level designs to 96–97%.

Answered on From thyristor to silicon carbide

Lithium batteries 8 questions

Do lithium battery cabinets need the same ventilation as lead-acid?

No. The EN IEC 62485-2 hydrogen formula is for lead-acid batteries. The AEC L6 lithium cabinets follow their own data: 0 to 40 °C, best 20 to 30 °C, front air inlet and rear or top outlet.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

How is an L6 lithium battery sized?

Twice: by power, at 10 kW per 40 or 50 Ah module and 5 kW per 100 Ah module, and by energy, from load × time with 95% battery and 95% inverter efficiency and a 10% reserve. The larger count wins.

Answered on L6 lithium battery sizing: modules, cabinets, room

How much does an L6 lithium cabinet weigh?

Full, 965 ± 20 kg with 40 Ah modules, 985 ± 20 kg with 50 Ah and 810 ± 24 kg with 100 Ah, on a 600 × 850 mm footprint: about 1,930 kg/m² for a full 50 Ah cabinet.

Answered on L6 lithium battery sizing: modules, cabinets, room

How long will a UPS last during a power cut?

From a few minutes to a few hours, set by the load in watts and the battery energy: the AEC All-in-One, for example, runs 15 to 60 minutes at its full 20 kW and up to 200 minutes at 6 kW, by its lithium modules. A small UPS at full load may last only a few minutes. Check the manufacturer's runtime table for your actual load.

Answered on UPS backup time: how to estimate and extend runtime

Is a lithium-ion UPS better than one with lead-acid batteries?

Not always. Lithium (LiFePO4) lasts more cycles, weighs less, takes less space and tolerates warm rooms better, but it costs more to buy. Lead-acid VRLA remains a sound choice in a cooled room where replacements are planned.

Answered on UPS batteries: VRLA vs lithium and how to choose

Can I put a lithium battery in a UPS designed for lead-acid?

Only if the UPS manufacturer approves it. Lithium needs a battery management system that works with the UPS charger and protections. Swapping chemistries without approval can damage the battery or leave the load unprotected.

Answered on UPS batteries: VRLA vs lithium and how to choose

How long will a home UPS last in a power cut?

About 11 minutes for the IST8 with its internal lithium battery, from its data sheet, and 2 minutes at full load for the standard IST3 1–3 kVA, much longer at light load.

Answered on UPS for home: protect devices, router and data

How long can a UPS keep equipment running?

A few minutes at full load with internal batteries: the standard 1–3 kVA IST3, for example, gives 2 minutes (AEC data), and much longer at part load. External battery cabinets or lithium systems extend this to hours.

Answered on What is a UPS and what does it do?

Installation, size and connections 32 questions

How do you calculate battery room ventilation for a UPS?

With EN IEC 62485-2: Q = 0.05 × n × Igas × Crt × 10⁻³ m³/h. n is the number of cells (six per 12 V block), Igas is 1 mA/Ah on float or 8 mA/Ah on boost for VRLA, and Crt is the capacity in Ah. For 64 blocks of 12 V 100 Ah (384 cells) that is 1.92 m³/h on float and 15.4 m³/h on boost: design for boost charge.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

How big must the ventilation openings of a battery room be?

For natural ventilation, an inlet and an outlet each with a free area of at least 28 × Q cm², with Q in m³/h. An AEC BB8 with 64 × 12 V 100 Ah blocks needs 15.4 m³/h on boost, so about 430 cm² per opening.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

Do VRLA batteries need ventilation if they are sealed?

Yes. VRLA blocks recombine almost all their gas inside, 99% for the OZ Power AGM blocks, but a small amount of hydrogen still escapes on charge, and more on boost charge. EN IEC 62485-2 sets the fresh air needed.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

Does the UPS power change the battery room ventilation?

No. The formula depends only on the number of cells and their capacity in Ah. A BB7 cabinet with 36 × 100 Ah blocks needs 8.64 m³/h on boost behind an IST7-60 or an IST7-160 alike.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

Is air conditioning enough for a battery room?

Not by itself. Air conditioning cools the air already in the room; the hydrogen rule asks for fresh air in and out. Plan both: fresh air for the batteries and cooling for the heat.

Answered on Battery room ventilation to EN IEC 62485-2 for VRLA

Which UPS should I choose for a server rack?

A 2U online rack UPS with a pure sine wave is the usual choice, sized at around half to three quarters of its watt rating. Add a network card so the servers shut down automatically when the battery runs low.

Answered on How to choose a UPS: type, runtime, phases and service

What are the most important UPS specifications?

Rated power in kVA and kW with the output power factor, the input voltage window, the battery voltage, the overload table and efficiency. Together they tell you whether the UPS can carry the load, cope with the grid and fit your battery. Environment data then tells you whether it fits the room.

Answered on UPS datasheet explained: every line, with examples

Does an L6 battery room need hydrogen ventilation?

No. The EN IEC 62485-2 hydrogen formula is for lead-acid batteries. The L6 needs air in at the front and out at the rear or top, 0 to 40 °C (best 20 to 30 °C), and 800 mm free in front and behind.

Answered on L6 lithium battery sizing: modules, cabinets, room

Do I need an electrician to install a three-phase UPS?

Yes. A three-phase UPS is hard-wired, with cables and breakers sized for the site. Single-phase units up to a few kVA, such as the IST3 1–3 kVA, often simply plug into a socket.

Answered on Single- or three-phase UPS: which does your site need?

Why is the neutral important in a three-phase UPS system?

The neutral carries the difference between unbalanced phase currents. With IT loads, third-harmonic currents add up in the neutral, so its current can approach or exceed the phase current. Size it at least as large as the phase conductors.

Answered on Three-phase UPS: configurations, sizing and installation

How big should a generator for a UPS be?

About 1.25 to 1.5 times the UPS input kVA, a rule of thumb commonly cited for a UPS with an active PFC input. Start from the UPS input power: load divided by efficiency, plus battery charging, then add any other loads on the generator. Always confirm the final size with the generator supplier.

Answered on UPS vs generator: how they differ and work together

Will a UPS protect my equipment from lightning?

Only in part: it protects against the surges, sags and noise that come with storms, but lightning needs a lightning protection system and surge protective devices (SPDs) in the electrical installation. They work together with the UPS.

Answered on UPS for blackouts and storms: what to know

Can I put a UPS in an outdoor camera cabinet?

Only if the cabinet keeps the UPS and battery within their operating temperature range. Heat shortens battery life a great deal. Where possible, feed remote cameras from a central UPS through the PoE switch instead.

Answered on UPS for CCTV and video surveillance systems

How do I size a UPS for a small data centre or server room?

Measure the real IT load in kW, add the growth you expect over the life of the UPS, and divide by about 0.8 to keep a working margin. For example, 72 kW of planned load needs about 90 kW of UPS capacity. Add one module or unit for N+1 if the site needs redundancy.

Answered on UPS for data centres: how to choose and plan

Can a rack UPS protect a server room?

Yes, for smaller loads. The IST3-J is a 2U single-phase online UPS from 1 to 10 kVA, and the IST9 puts a 10–40 kVA three-phase online UPS into a 3U rack chassis. Above a few tens of kW, or when the load will grow, a modular UPS is usually the better fit.

Answered on UPS for data centres: how to choose and plan

Should the UPS batteries be in the server room?

Yes, if the temperature is controlled, but larger sites use a separate room. A widely used rule of thumb says VRLA battery life roughly halves for every 8 °C above 25 °C. Lithium batteries such as the L6 system take less floor space.

Answered on UPS for data centres: how to choose and plan

Can a UPS power my whole house?

Yes, but it is an electrical installation, not a plug-in device. For a typical 3 kW supply you need a 3 kW class UPS, such as the IST8 3 kVA, wired into the consumer unit by an electrician. Heavy loads such as ovens, water heaters and heat pumps are usually left off the protected circuits.

Answered on UPS for home: protect devices, router and data

Does a home UPS need an electrician?

No, not a plug-in UPS of 1–3 kVA, which goes into a wall socket. A UPS that feeds the whole house, or a 6–10 kVA unit on terminals, must be installed by a qualified electrician, who checks protection devices and earthing.

Answered on UPS for home: protect devices, router and data

What is a medical UPS?

The term usually means a UPS used to protect medical and hospital loads, normally an online double-conversion unit. A UPS is not itself medical electrical equipment, so its position and connection near patients must follow the installation rules. Check which standards a specific model is declared to.

Answered on UPS for hospitals and healthcare facilities

What is an industrial UPS?

An industrial UPS is an uninterruptible power supply built for factories and process plants. It is usually an online double-conversion unit that tolerates poor grids, inductive and inrush loads, dust and heat. It protects PLCs, control systems and critical machines from power cuts and disturbances.

Answered on Industrial UPS: protecting PLCs, motors and processes

What IP rating does an industrial UPS need?

Most UPS are IP20 and are designed for a clean, dry electrical room. If the plant is dusty or wet, install the UPS in a separate room or a suitable enclosure rather than on the shop floor. The AEC IST7-T reaches IP21 with an optional top cover.

Answered on Industrial UPS: protecting PLCs, motors and processes

How much heat does a UPS produce?

A UPS gives off heat equal to its losses: load × (1/efficiency − 1). At 96% efficiency, a 20 kW load produces about 0.83 kW of heat. At 99% in ECO mode, the same load produces about 0.20 kW.

Answered on UPS heat output: BTU, cooling and room temperature

How do I convert UPS watts to BTU?

Multiply the heat output in watts by 3.412 to get BTU per hour. For example, 3,600 W of UPS losses is about 12,300 BTU/h. Use the losses, not the UPS rating or the load itself.

Answered on UPS heat output: BTU, cooling and room temperature

What is the ideal UPS operating temperature?

AEC's IST7, IST9 and IST6 120 ranges are specified for −5 to 40 °C, and AEC recommends 20-25 °C for the IST7 10-40 kVA. If batteries share the room, aim for about 20-25 °C, because battery life drops quickly at higher temperatures.

Answered on UPS heat output: BTU, cooling and room temperature

What temperature should a UPS battery room be?

Around 20-25 °C for VRLA batteries. Their life roughly halves for every 8 °C above 25 °C, and below about 20 °C the available runtime falls. A temperature probe lets the UPS adjust the charge voltage.

Answered on UPS heat output: BTU, cooling and room temperature

Does a UPS room need air conditioning?

Yes, usually, unless the losses are small and the room can lose heat naturally. Calculate the losses in BTU/h, add the other heat sources and ask a cooling engineer. Also decide whether the cooling must keep running during a power cut.

Answered on UPS heat output: BTU, cooling and room temperature

Do sealed VRLA batteries need ventilation?

Yes. VRLA batteries recombine most of their gas, but they can still release small amounts of hydrogen, especially when charging. EN IEC 62485-2 sets the ventilation requirements for stationary lead-acid batteries.

Answered on UPS heat output: BTU, cooling and room temperature

How much space does a UPS need around it?

800 mm in front, behind and above for an AEC IST7 60–200 kVA; at least 300 mm behind for an IST7 10–40 kVA; 800 mm in front and behind and 500 mm above for an IST6 30–120 kVA. Each range's manual gives its own figures.

Answered on UPS installation clearances: what to check on site

What is the operating gangway in front of a UPS?

On the face where switches and terminals are worked, HD 60364-7-729 (CEI 64-8 section 729 in Italy) asks for at least 700 mm, the door open at 90° plus 500 mm, and a pulled-out module plus 500 mm. In front of an IST6 30–120 kVA that makes 1,200 mm.

Answered on UPS installation clearances: what to check on site

How much does a UPS battery cabinet load the floor?

About four times as much as the UPS: an AEC BB7 with 36 × 12 V 100 Ah blocks loads the floor at 1,992 kg/m² and a BB8 with 64 × 100 Ah at 1,978 kg/m², against about 490 kg/m² for an IST7-200.

Answered on UPS installation clearances: what to check on site

Where do cables enter AEC three-phase UPS, top or bottom?

The IST7 60–200 kVA takes them from below on every model. The IST6 30–120 and 200–500 kVA take them from below as standard, with top entry as an option; the IST6 400–1200 kVA from the top, with bottom entry through a side wiring cabinet.

Answered on UPS installation clearances: what to check on site

Can a UPS be installed on a raised floor?

Yes, on a stand built for its weight, not on the floor tiles. The IST7 60–200 kVA and L6 manuals also require concrete or another non-combustible floor.

Answered on UPS installation clearances: what to check on site

Communication and monitoring 6 questions

How do I read a UPS datasheet?

Go through it in order: rated power, input, battery, output, efficiency, environment, communication and standards. For each line, compare the figure with your load and your site. Always read the footnotes, because they hold derating rules and test conditions.

Answered on UPS datasheet explained: every line, with examples

Should I unplug equipment during a storm if I have a UPS?

No, not with an online UPS: the equipment is supplied by the inverter and filtered at all times. For long storms or unattended sites, set up automatic shutdown so systems close in order before the battery runs out.

Answered on UPS for blackouts and storms: what to know

What is the best UPS for security cameras?

The best UPS is the one sized for your whole chain and your site's outages. For most professional systems that means an online double-conversion UPS with sine-wave output, remote alarms and the option of external batteries.

Answered on UPS for CCTV and video surveillance systems

Can a UPS report its status to the building management system?

Yes. Ranges such as the IST7-T have RS232 / RS485 Modbus and configurable dry contacts as standard, and an SNMP card is available as an option.

Answered on UPS for hospitals and healthcare facilities

How does an industrial UPS connect to a PLC?

Through dry contacts wired to PLC inputs, or through Modbus RTU over RS485. Dry contacts signal states such as mains failure or battery low. Modbus also reads values such as load and remaining runtime.

Answered on Industrial UPS: protecting PLCs, motors and processes

What does EPO mean on a UPS?

EPO means emergency power off. It is an input, often wired to a red button, that cuts the UPS output at once. It is different from remote OFF, which is a normal control signal.

Answered on UPS glossary: 87 UPS terms and acronyms explained

Efficiency and operation 37 questions

Is an online UPS always better than a line-interactive one?

Not for every load: online double conversion gives zero transfer time and constant output, so it is the right choice for servers and sensitive loads. A line-interactive unit can be enough for simple home or small office equipment.

Answered on How to choose a UPS: type, runtime, phases and service

What does "up to 96% efficiency" mean on a UPS datasheet?

It is the best value, measured at one operating point. Efficiency is usually lower at light load. Ask for efficiency at 25%, 50%, 75% and 100% load and use the value closest to your real load.

Answered on UPS datasheet explained: every line, with examples

What is an isolation transformer UPS?

It is a UPS with a transformer in the power path that separates the output electrically from the input. Energy crosses the transformer magnetically, so there is no direct copper connection between mains and load. The transformer secondary provides a new neutral at the output.

Answered on Isolation transformer UPS: when you need one

What is the difference between a transformer based UPS and a transformerless UPS?

A transformer-based UPS has an isolation transformer, usually at the output, giving galvanic isolation and a new neutral. A transformerless UPS produces the output directly from the inverter, so it is lighter, smaller and usually more efficient. The transformer-based design suits industrial sites, harsh supplies and specific earthing needs.

Answered on Isolation transformer UPS: when you need one

Does a UPS need an isolation transformer?

Not always. Most IT rooms and offices on a good supply work well with a transformerless UPS. An isolation transformer is worth it when you need a new neutral, a different earthing system downstream, protection from a poor supply or a voltage change.

Answered on Isolation transformer UPS: when you need one

Does an isolation transformer UPS give isolation on bypass?

Only if the bypass is also routed through a transformer. In many designs, including those where the transformer sits on the inverter output, the bypass feeds the load from the mains directly. In that case isolation applies while the load is on the inverter.

Answered on Isolation transformer UPS: when you need one

Is a transformer UPS less efficient?

Yes, generally, because the transformer adds core losses whenever it is energised and winding losses that grow with load. The difference depends on the design and the load level. The extra losses also become heat that the room cooling must remove.

Answered on Isolation transformer UPS: when you need one

Can an isolation transformer UPS be used in hospitals?

Yes, as part of a hospital installation, where isolation and special earthing rules often apply. Compliance depends on the whole system, assessed by the designer against IEC 60364-7-710 and national rules, not on the UPS alone. Ask for the full requirements before choosing equipment.

Answered on Isolation transformer UPS: when you need one

Is a modular UPS less efficient at low load?

Not necessarily. Functions such as redundancy sleep rest spare modules at light load, so the working modules run closer to their best efficiency. Always compare efficiency at your real load.

Answered on Modular UPS: how to grow power module by module

Is a three-phase UPS more efficient?

Not because of the phases: efficiency depends on the design. Check the data sheet: the IST7 10–40 kVA, for example, reaches up to 96% in double conversion.

Answered on Single- or three-phase UPS: which does your site need?

What is a 3 phase UPS?

A 3 phase UPS is an uninterruptible power supply fed from a three-phase 400 V supply. It keeps critical loads running through mains failures and disturbances, usually with online double conversion. It is the normal choice for loads above about 10-20 kVA.

Answered on Three-phase UPS: configurations, sizing and installation

When should I choose a UPS with an isolation transformer?

Choose one when the load or site needs galvanic isolation between input and output, for example on industrial sites or harsh grids. The transformer can also provide a locally derived neutral. Otherwise a transformerless UPS is smaller and generally more efficient.

Answered on Three-phase UPS: configurations, sizing and installation

UPS vs generator: which one do I need?

For critical loads such as servers and networks you usually need both. The UPS gives instant power with no break, and the generator carries outages that last longer than the batteries. For short outages at home or in a small office, a UPS alone is often enough.

Answered on UPS vs generator: how they differ and work together

Can a generator replace a UPS?

Not for sensitive equipment. A standby generator typically needs several seconds to start and take the load, and computers and network devices reset in that time. A UPS bridges that gap and also filters out disturbances.

Answered on UPS vs generator: how they differ and work together

What is a good UPS efficiency?

For a three-phase online UPS in double conversion, efficiency of about 94% to 97% is common, and the best modern modular designs reach about 97-98% at their best load point. These are typical ranges, not rules. In ECO mode efficiency is usually about 99%. What matters most is the efficiency at your real load, so ask for figures at 25%, 50%, 75% and 100% load.

Answered on UPS efficiency and ECO mode: losses and energy savings

What is UPS ECO mode?

UPS ECO mode feeds the load through the static bypass while the mains voltage and frequency stay inside a set window. The inverter waits on standby and takes over when the mains goes out of tolerance. It raises efficiency to about 99%, but the load is no longer isolated from the mains as in online double conversion.

Answered on UPS efficiency and ECO mode: losses and energy savings

Is ECO mode safe for servers?

Not as a default: in ECO mode the servers run on the bypass, see the mains disturbances inside the ECO window and take a short transfer when the mains leaves it, so AEC recommends double conversion for them. Some IT power supplies tolerate that on a stable mains; on weak grids, generator supplies or very sensitive equipment it is not suitable. Check the load's tolerance and the ECO window before enabling it.

Answered on UPS efficiency and ECO mode: losses and energy savings

How do I calculate UPS losses?

Use losses (kW) = P × (1/η − 1), where P is the load in kW and η is the efficiency as a decimal. For example, 100 kW at 96.5% gives 100 × (1/0.965 − 1) = 3.63 kW. Multiply by the hours of operation to get kWh per year.

Answered on UPS efficiency and ECO mode: losses and energy savings

Why is UPS efficiency lower at light load?

Part of the losses is fixed: controls, fans and the converters themselves draw power whatever the load. At light load those fixed losses are large compared with the power delivered, so efficiency falls. Right-sizing, or using a modular UPS with redundancy sleep, keeps the loading closer to the efficient zone.

Answered on UPS efficiency and ECO mode: losses and energy savings

Does a more efficient UPS reduce cooling needs?

Yes. Every kW of UPS loss becomes a kW of heat in the room, which the cooling system must remove. Lower losses mean less heat and less electrical power for the cooling, on top of the saving in the UPS itself.

Answered on UPS efficiency and ECO mode: losses and energy savings

Can a UPS replace a generator?

No. A UPS bridges minutes and removes the break when the mains fails; a generator supplies hours. For long outages the two work together: the UPS carries the load while the generator starts.

Answered on UPS for blackouts and storms: what to know

Is a line-interactive UPS enough for CCTV?

Only for small systems on a stable mains, and only with a sine-wave output. For larger systems, unstable supplies or generator sites, an online double-conversion UPS gives 0 ms transfer and a cleaner supply.

Answered on UPS for CCTV and video surveillance systems

Is an online UPS worth it at home?

Yes, if you work from home, have a NAS or a small server, or your supply is unstable: an online UPS such as the IST3 gives zero transfer time and a clean sine wave. For a simple PC a line-interactive unit may be enough.

Answered on UPS for home: protect devices, router and data

Why do hospitals need a UPS if they have generators?

A generator takes seconds to start and reach stable output. A UPS supplies critical loads without any break during that time and filters disturbances at all times. It also covers the case where the generator fails to start at the first attempt.

Answered on UPS for hospitals and healthcare facilities

Can a UPS run motors?

Yes, within limits. Check the starting current against the UPS overload rating, because direct-on-line motors often draw 5 to 8 times their rated current while starting. A soft starter or variable-speed drive makes this much easier.

Answered on Industrial UPS: protecting PLCs, motors and processes

What is THDi in UPS terms?

THDi is the total harmonic distortion of the input current, as a percentage. A low value, such as 3% to 5%, means the UPS draws a near-sinusoidal current. That puts less stress on cables, transformers and generators.

Answered on UPS glossary: 87 UPS terms and acronyms explained

What is an online UPS?

An online UPS, or online uninterruptible power supply, feeds the load from its inverter at all times. The mains is first converted to DC and then rebuilt as a new sine wave, so the load never sees the grid directly. When the mains fails there is no transfer time, because the inverter keeps running from the battery.

Answered on Online UPS vs line-interactive vs offline: UPS types

What is the difference between an online UPS and a line-interactive UPS?

A line-interactive UPS feeds the load from the mains and corrects the voltage with an automatic voltage regulator, but does not correct the frequency. When the mains fails it switches to battery with a short break of a few milliseconds. An online UPS rebuilds voltage and frequency continuously and has 0 ms transfer from mains to battery.

Answered on Online UPS vs line-interactive vs offline: UPS types

Is ECO mode safe to use on an online UPS?

Only for loads that tolerate the raw mains, on a site where the mains is stable; AEC's normal mode is double conversion. In ECO mode the load is fed through the bypass, so it sees mains disturbances within the set window, and the UPS transfers to the inverter when the mains leaves that window. For medical, sensitive IT or generator-fed loads, double conversion is usually the better choice.

Answered on Online UPS vs line-interactive vs offline: UPS types

Is an 'online interactive' UPS the same as an online UPS?

No. Names like 'online interactive' are marketing labels and usually describe a line-interactive design. Check the IEC 62040-3 classification on the data sheet: only VFI indicates online double conversion.

Answered on Online UPS vs line-interactive vs offline: UPS types

Does a generator remove the need for a UPS or CPSS?

No. A generator takes time to start, so a UPS is still needed to keep IT loads running without a break. Unless national rules state otherwise, the CPSS must supply the safety loads for the required duration on its own.

Answered on UPS vs CPSS: which one does a building need?

What is a UPS power supply used for?

It protects computers, servers, network equipment, medical devices, industrial controls and security systems from power cuts, sags, surges and electrical noise. It gives time to ride through short outages, start a generator or shut systems down without losing data.

Answered on What is a UPS and what does it do?

Does a UPS protect against surges?

Yes. An online double-conversion UPS supplies the load from its inverter at all times, so surges, sags and noise on the mains do not reach the equipment. Line-interactive units correct sags and surges with a voltage regulator, but less completely.

Answered on What is a UPS and what does it do?

Do I need an online UPS?

Yes, for servers, network equipment, medical devices and any load that cannot tolerate a break: online double conversion has no transfer time and gives a stable output. For a simple home PC, a line-interactive unit can be enough.

Answered on What is a UPS and what does it do?

At which loads is the efficiency measured?

At 25, 50, 75 and 100% of the rated power, with the methods of EN 62040-3, in normal mode. The Code also asks for information on behaviour and efficiency in higher-efficiency modes such as ECO.

Answered on EU Code of Conduct on UPS energy efficiency

Why does silicon carbide raise UPS efficiency?

SiC has a band gap of 3.26 eV and a critical field about ten times silicon's: it blocks high voltage in a thin chip, conducts with little resistance and switches fast with low losses. Double-conversion UPS with SiC reach 98–99%.

Answered on From thyristor to silicon carbide

Are thyristors still used in UPS?

Yes, where a rugged switch at line frequency is needed: the static bypass of every online UPS is a pair of thyristors in anti-parallel, which moves the load to the utility without a break.

Answered on From thyristor to silicon carbide

Standards and certification 10 questions

What is EN 50171?

EN 50171 is the European standard for central power supply systems for safety equipment. It applies to systems permanently connected to low-voltage AC supplies that use batteries as the alternative source. It covers topics such as autonomy, battery, recharge, monitoring, enclosure and tests.

Answered on CPSS to EN 50171: what it asks and how to size one

Which AEC products comply with EN 50171?

AEC offers the tower CPSS 1–10 kVA and the CPSS 10–200 kVA, both designed to meet the requirements of EN 50171, with a structure compliant with CEI EN 62040. Both hold a constant 120% overload and recharge the battery in under 12 hours.

Answered on CPSS to EN 50171: what it asks and how to size one

What type of UPS is used in a data centre?

Data centres use online double-conversion UPS, class VFI under IEC 62040-3. The inverter supplies the load all the time, so in normal operation mains disturbances do not reach the servers and there is no transfer time when the mains fails. Larger sites usually choose modular systems for growth and redundancy.

Answered on UPS for data centres: how to choose and plan

What are group 0, 1 and 2 medical locations?

They are classes in IEC 60364-7-710. Group 0 uses no applied parts, group 1 uses applied parts where an interruption does not threaten life, and group 2 covers areas such as operating theatres and intensive care, where an interruption could endanger life.

Answered on UPS for hospitals and healthcare facilities

Is a CPSS the same as a hospital UPS?

No. A central power supply system to EN 50171 feeds emergency lighting and other safety equipment, with requirements set by that standard. A UPS keeps medical and IT loads running. Many hospitals need both.

Answered on UPS for hospitals and healthcare facilities

What does VFI mean on a UPS?

VFI means voltage and frequency independent. It is the IEC 62040-3 class in which the UPS output does not depend on the mains voltage or frequency. Online double conversion UPS belong to this class.

Answered on UPS glossary: 87 UPS terms and acronyms explained

What do VFI, VI and VFD mean?

They are the output dependency classes of IEC 62040-3. VFI means the output is independent of changes in supply voltage and frequency (online double conversion). VI means the voltage is regulated but the output depends on frequency (line-interactive), and VFD means the output depends on both (offline or standby).

Answered on Online UPS vs line-interactive vs offline: UPS types

Can I use a UPS for emergency lighting?

Not where EN 50171 applies. Safety lighting must be supplied by a CPSS that meets that standard. A standard UPS is designed for equipment continuity, not for safety systems.

Answered on UPS vs CPSS: which one does a building need?

Does a CPSS have to comply with EN 62040?

No, EN 50171 is the standard a CPSS is declared to. Because a static CPSS uses the same converter technology as a UPS, manufacturers often refer to the IEC / EN 62040 series as well: AEC's CPSS ranges, for example, are declared with a structure compliant with CEI EN 62040. Check the project requirements with the system designer.

Answered on UPS vs CPSS: which one does a building need?

Is the EU Code of Conduct on UPS mandatory?

No. It is a voluntary commitment run by the European Commission's Joint Research Centre (JRC): a signatory commits to its minimum efficiencies and reports the data of its UPS. A specification can still ask for the Code's values as a requirement.

Answered on EU Code of Conduct on UPS energy efficiency

Warranty, service and maintenance 7 questions

Can I add modules without switching off the load?

Yes, on the IST6: power modules are hot-swappable, inserted and removed with the load running. Modules and further cabinets are added and configured by AEC service.

Answered on Modular UPS: how to grow power module by module

How often should a UPS be serviced?

Typical practice is a monthly visual check by site staff, quarterly checks of the UPS and a full service visit by a qualified technician at least once a year. Critical or warm sites usually need shorter intervals. Always follow the manufacturer's manual for your UPS.

Answered on UPS maintenance: batteries, checks and schedule

What does an external maintenance bypass switch do?

It feeds the load directly from the mains while the UPS is isolated, so the UPS can be serviced, repaired or replaced without switching the load off. It is mounted between the UPS and the load. It must be compatible with the UPS and operated in the order the manual gives.

Answered on UPS maintenance: batteries, checks and schedule

Can I do UPS maintenance myself?

Only the checks from outside: site staff can do visual checks, read the display and event log and run battery tests from the front panel. Work inside the UPS or battery cabinet involves dangerous DC voltages and is for qualified, authorised technicians only.

Answered on UPS maintenance: batteries, checks and schedule

Can a UPS run my fridge during a power cut?

Not a small one: a home UPS of 1–3 kVA is not designed for fridges or freezers, which draw high starting currents. A larger whole-home UPS can feed them if its overload limits cover the start-up, but runtime is still minutes. For long outages a generator is the right tool.

Answered on UPS for home: protect devices, router and data

What is the difference between a bypass and a maintenance bypass?

The static bypass is an automatic electronic path that feeds the load from the mains on overload or inverter fault. The maintenance bypass is a manual switch that feeds the load while the UPS is isolated for service. The IST7 10–40, for example, has both.

Answered on UPS glossary: 87 UPS terms and acronyms explained

Does a maintenance bypass provide redundancy?

No. A maintenance bypass routes the load around the UPS so it can be serviced, but during that time the load runs on raw mains with no protection against an outage. It complements redundancy by making maintenance possible without a shutdown.

Answered on UPS redundancy: N+1 or 2N, and how much a site needs

About the product and AEC 3 questions

Where can I get a UPS datasheet PDF from AEC?

The technical data for each range is on its product page, for example the IST7 10–40. For a PDF datasheet or catalogue, contact AEC through the contact form. You can also ask for help reading the data for your project.

Answered on UPS datasheet explained: every line, with examples

Can I keep my internet connection during a blackout?

Yes, if the router, modem and any network switch are on the UPS. These draw little power, so even a small UPS can keep them running for a useful time.

Answered on UPS for blackouts and storms: what to know

Do cameras need a UPS if the recorder has one?

Yes. If the cameras lose power, the recorder has nothing to record. Protect cameras or the PoE switch that feeds them, the recorder and the network devices together.

Answered on UPS for CCTV and video surveillance systems

Still a question?