Choosing, sizing and ordering 5 questions
How many cabinets and modules do I need for my UPS?
From the AEC sizing tables, a UPS up to 100 kW needs 1 cabinet with 10 × 40 Ah modules for 10 minutes. Up to 200 kW, 1 cabinet with 20 × 50 Ah modules for 15 minutes; up to 20 kW, 1 cabinet with 8 × 100 Ah modules for 2 hours. Plan a 10% reserve (actual backup = theoretical × 0.9); AEC engineers confirm module type, quantity and reserve for each project.
Answered on L6 Lithium
Which UPS can the L6 work with?
The L6 is designed for the AEC IST7 and IST6 series, from 6 to 1200 kVA. Its DC/DC converters deliver 240, ±240 or 480 V DC to follow the UPS battery input, and the touch screen talks to the UPS over RS485.
Answered on L6 Lithium
How many L6-100 modules for 2 hours at 10 kW?
Five modules in one cabinet, from the L6 sizing table (10 kW: 3 modules for 1 h, 5 for 2 h, 9 for 4 h, the 10% reserve included). AEC sizes every project.
Answered on L6-100
Why is the L6-100 cabinet rated only 60 kW?
Each 100 Ah module delivers 5 kW through its DC/DC converter and the cabinet holds twelve: 60 kW. The 40 / 50 Ah modules deliver 10 kW each, twenty per cabinet, for 200 kW, but store less energy per module.
Answered on L6-100
Can L6-40 modules be replaced with the UPS running?
Yes. A faulty module leaves the system on its own and the others keep supplying the UPS; it is replaced online in about 5 minutes. New and old modules work together, so capacity can also be added later.
Answered on L6-40
Backup time and batteries 4 questions
Which L6 module should I choose for my backup time?
The 40 Ah module (6C cells) is for short backup of 10 or 20 minutes, the 50 Ah module (4C) for 15 or 30 minutes, and the 100 Ah module (1C) for long backup of 1, 2 or 4 hours. A full cabinet gives 10 minutes (40 Ah), 15 minutes (50 Ah) or 1 hour (100 Ah) at rated power.
Answered on L6 Lithium
How many L6-40 modules for 10 minutes at 100 kW?
From AEC's sizing table: one cabinet with 10 modules for UPS up to 100 kW at 10 minutes, and one cabinet with 20 modules for 20 minutes. The 10% reserve is included; AEC confirms the number for each project.
Answered on L6-40
L6-40 or L6-50?
Same cabinet, same 10 kW per module, same 200 kW per cabinet. The L6-50 stores 58 kWh instead of 41 and gives 15 / 30 minutes where the L6-40 gives 10 / 20, with about 10% more modules. Choose by the backup time required.
Answered on L6-50
How many L6-50 cabinets for 30 minutes at 400 kW?
The L6 sizing table gives five cabinets with 85 modules for 400 kW at 30 minutes, and three cabinets with 43 modules at 15 minutes. Above one cabinet, one master and its slave cabinets work in parallel; from four cabinets a combiner joins them.
Answered on L6-50
Lithium batteries 1 question
How long do the L6 lithium batteries last?
The LFP cells are rated for 5,000 cycles at 50% depth of discharge. In AEC's comparison, a lead-acid battery is replaced three times during the life of a UPS, while the L6 needs no replacement and a faulty module is changed on its own.
Answered on L6 Lithium
Installation, size and connections 3 questions
What are the L6 cabinet size, energy and weight?
Every cabinet measures 600 × 850 × 2000 mm. With 20 modules it stores 41 kWh (40 Ah) or 58 kWh (50 Ah) at 200 kW rated power, weighing 965 or 985 kg; with 12 × 100 Ah modules it stores 69 kWh at 60 kW and weighs 810 kg.
Answered on L6 Lithium
What are the installation requirements for the L6?
Install on a concrete or non-flammable floor, at 0–40 °C and 5–95% relative humidity non-condensing, below 4000 m (derating above 2000 m), with air inlets and outlets kept clear. Modules are shipped at 20–50% state of charge and stored at −10 … +45 °C.
Answered on L6 Lithium
L6 Lithium: how big is each model and how much does it weigh?
Width × depth × height and weight, model by model:
| Model | Size | Weight |
|---|---|---|
| L6-40 | 600 × 850 × 2000 mm | 965 ± 20 kg with 20 modules |
| L6-50 | 600 × 850 × 2000 mm | 985 ± 20 kg with 20 modules |
| L6-100 | 600 × 850 × 2000 mm | 810 ± 24 kg with 12 modules |
Size and weight from the EMEA 2026 catalogue.
Each model's own page, linked in the table, gives its full answer and data.
Warranty, service and maintenance 1 question
Can modules be replaced or added without switching off?
Yes: modules are hot-swappable and replaced online in about 5 minutes, and a faulty module leaves the system on its own while the others keep working. New and old modules work together, so capacity can grow up to 15 cabinets in parallel.
Answered on L6 Lithium
By range
Still a question?
Tell us the load, the supply and the backup time you need: AEC answers with the model and the batteries.