Can the IST9 supply single-phase loads from a three-phase input?

Yes: every IST9 works in 3/3 or 3/1 mode, and the 10–20 kVA models also in 1/1. The mode is set with connector jumpers on the rear terminals and on the touch screen.

Answered on IST9

Can IST9 units work in parallel for redundancy?

Yes, with the optional parallel card and port (CAN communication between units) for N+1 redundancy, where the total load stays within N times one unit. A faulty unit leaves the system automatically, and units join or leave online.

Answered on IST9

Can the IST9 10 kVA run on a 120 V system?

Yes. In low-voltage mode (110 / 115 / 120 V phase, 190 / 200 / 208 V line) the 10 kVA keeps 10 kVA / 10 kW, at 94% efficiency. Full load holds from 90 to 155 V phase voltage.

Answered on IST9 10 kVA

Is the IST9 15 kVA bigger than the 10 kVA?

No. The 10, 15 and 20 kVA share one chassis: 438 × 535 × 130 mm (3U) and 18.4 kg. Only the 30 and 40 kVA are deeper (720 mm).

Answered on IST9 15 kVA

What does the IST9 20 kVA deliver in low-voltage mode?

10 kVA / 10 kW: in low-voltage mode (110 / 115 / 120 V phase) the catalogue halves the 20 kVA's rating. In high-voltage mode (220 / 230 / 240 V phase) it gives the full 20 kVA / 20 kW.

Answered on IST9 20 kVA

What is the ordering code of the AEC IST9 20 kVA?

In the EMEA 2026 catalogue the AEC IST9 20 kVA is listed as IST9-20, IST9-20-[n]X9; AEC gives the full code, batteries included, from the load and the backup time.

Answered on IST9 20 kVA

How loud is the IST9 30 kVA?

At 20–25 °C: up to 55 dB at half load, 58 dB at 75% and 60 dB at full load. Fan speed follows the load, so a lightly loaded unit is quieter.

Answered on IST9 30 kVA

Can several IST9 40 kVA work in parallel?

Yes, with the parallel kit PAR-IST9 (parallel card and 2 m cable, CAN communication). Units are started one by one, then joined; a faulty unit leaves the system with an alarm and can be serviced online.

Answered on IST9 40 kVA

Backup time and batteries 4 questions

Which batteries does the IST9 use, and how is backup time extended?

The battery string is set on site: in high-voltage mode ±48 to ±120 cells of 2 V (default ±96), that is ±96 to ±240 V DC, lead-acid or the approved lithium system via the protocol card. For the IST9 20 kVA, AEC codes combine the UPS with 2, 4, 6, 8 or 10 BBJ2 rack cabinets, from 32 to 160 × 12 V 9 Ah, always mounted below the UPS.

Answered on IST9

IST9: how long does each model run on battery?

Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):

ModelFull loadBackup at full loadAt half loadFor exampleIts backup
IST9 10 kVA10 kW5 to 56 minutes17 to 146 minutes32 × 12 V 9 Ah · 2 × 16 (IST9-10-32X9)5 min at 100%, 17 at 50%
IST9 20 kVA20 kW2 to 24 minutes5 to 56 minutes32 × 12 V 9 Ah · 2 × 16 (IST9-20-32X9)2 min at 100%, 5 at 50%

For other loads and batteries use the backup-time tool.

Each model's own page, linked in the table, gives its full answer and data.

How long does the IST9 15 kVA run on battery?

At 15 kW: 3 to 34 minutes with 2 to 10 BBJ2 cabinets (32 to 160 × 12 V 9 Ah). At 7.5 kW: 9 to 86 minutes. AEC sizes every system for the real load.

Answered on IST9 15 kVA

How many batteries can the IST9 20 kVA have?

With BBJ2 rack cabinets (3U, up to 16 × 12 V 9 Ah each): 32, 64, 96, 128 or 160 batteries with 2 to 10 cabinets (codes IST9-20-[n]X9). The battery box always goes below the UPS, with a DC battery switch between battery and UPS.

Answered on IST9 20 kVA

Lithium batteries 1 question

Can the IST9 40 kVA use lithium batteries?

Yes: the battery type is set on the screen, lead-acid or the approved lithium battery system, which talks to the UPS through the optional lithium protocol card (RS485 on RJ45).

Answered on IST9 40 kVA

Installation, size and connections 5 questions

What are the IST9 dimensions and weights?

Every IST9 is 438 mm wide and 130 mm (3U) high, for a 19-inch rack or standing as a tower. It measures 438 × 535 × 130 mm and 18.4 kg for 10–20 kVA, 438 × 720 × 130 mm and 34.1 / 34.2 kg for 30–40 kVA. The touch screen turns automatically between landscape and portrait.

Answered on IST9

What should be planned for the IST9 installation?

The IST9 runs at −5 … 40 °C, up to 2000 m. Size breakers at 1.5–2 times the maximum input current without leakage protection, with a DC breaker rated above 250 V DC and a DC battery switch between battery and UPS; the optional distribution module adds input, bypass, output and maintenance bypass breakers.

Answered on IST9

Which breakers does the IST9 10 kVA need?

In 3/3: 32 A 3P on AC input, bypass and output, 100 A 3P on the battery. In 3/1: 63 A 1P on bypass and output. In 1/1: 80 A 1P on the input. Breakers 1.5–2 times the maximum input current, without leakage protection.

Answered on IST9 10 kVA

IST9: how big is each model and how much does it weigh?

Width × depth × height and weight, model by model:

ModelSizeWeight
IST9 10 kVA438 × 535 × 130 mm (3U)18.4 kg
IST9 15 kVA438 × 535 × 130 mm (3U)18.4 kg
IST9 20 kVA438 × 535 × 130 mm (3U)18.4 kg
IST9 30 kVA438 × 720 × 130 mm (3U)34.1 kg
IST9 40 kVA438 × 720 × 130 mm (3U)34.2 kg

Size and weight from the EMEA 2026 catalogue.

Each model's own page, linked in the table, gives its full answer and data.

Will the IST9 30 kVA fit my rack?

Yes, if it has 3U and 720 mm of usable depth, plus room at the rear for terminals and cables. The 10–20 kVA models are 535 mm deep. Its weight, 34.1 kg, calls for rails rated for it.

Answered on IST9 30 kVA

Communication and monitoring 1 question

Which communication options does the IST9 have?

An RS232 port, the EPO and a programmable input (IN.1) are standard. The intelligent slot takes an SNMP card for web monitoring, an RS485 + dry-contact card (3 outputs, 2 inputs) or the protocol card for the approved lithium battery system.

Answered on IST9

Efficiency and operation 1 question

How efficient is the IST9?

Up to 96% in online double conversion and 99% in ECO mode, with output power factor 1 (kVA = kW). At a 20 kW load running 24/7, AEC's indicative calculation gives about 7,300 kWh lost per year in double conversion against 1,770 kWh in ECO mode.

Answered on IST9

Still a question?