Choosing, sizing and ordering 3 questions
Which IST8 model do I need for my load?
The output power factor is 1, so each kVA is a usable kW: the IST8-1 delivers 1000 W, the IST8-2 2000 W and the IST8-3 3000 W. Unbalanced, half-wave rectified or inductive loads such as air conditioners, motors, drills or fluorescent lamps must not be connected.
Answered on IST8
IST8-1 or IST3-J 1 kVA?
Same 2U chassis and depth. The IST8-1 has a lithium-ion battery, the same 1000 W, weighs 8.9 kg instead of 14 kg and works up to 60 °C; the IST3-J 1 kVA uses 12 V 9 Ah lead-acid batteries and can be extended with battery boxes.
Answered on IST8-1
Backup time and batteries 4 questions
What battery does the IST8 use?
A lithium-ion battery built into the 2U chassis, with no separate battery box. It offers up to 8 years of service life and up to 1000 charge / discharge cycles.
Answered on IST8
What backup time does the IST8 give?
The internal battery gives 11 minutes of backup time, with a maximum charging current of 4 A. Down to 120 V of mains the battery does not discharge, so it stays at 100% for real outages.
Answered on IST8
IST8: how long does each model run on battery?
Model by model, with the AEC battery options in each model's table (the battery chosen sets the figure):
| Model | Full load | Backup at full load | At half load | For example | Its backup |
|---|---|---|---|---|---|
| IST8-1 | 1 kW | 12 minutes | 42 minutes | built-in lithium battery (IST8-1-Li) | 12 min at 100%, 42 at 50% |
| IST8-2 | 2 kW | 12 minutes | 42 minutes | built-in lithium battery (IST8-2-Li) | 12 min at 100%, 42 at 50% |
| IST8-3 | 3 kW | 12 minutes | 42 minutes | built-in lithium battery (IST8-3-Li) | 12 min at 100%, 42 at 50% |
For other loads and batteries use the backup-time tool.
Each model's own page, linked in the table, gives its full answer and data.
How long does the IST8-3 run on battery?
AEC's data give 12 minutes at full load and 42 at half load with the internal lithium-ion battery (the catalogue prints 11 minutes, without a load); there is no external battery option. For longer backup in a rack, look at the IST3-J with battery boxes.
Answered on IST8-3
Installation, size and connections 6 questions
What are the IST8 dimensions and weights?
All ratings are 2U high and 438 mm wide for a 19-inch rack: the 1 kVA measures 438 × 423 × 86 mm (8.9 kg), the 2 and 3 kVA 438 × 570 × 87 mm (13.6 and 16.1 kg). The same unit mounts in a rack with two angle irons or stands as a tower on two supports.
Answered on IST8
Which voltages, inlets and outlets does the IST8 have?
The input accepts 120–295 V AC at 50 / 60 Hz, and the output is 208, 220 or 230 V ± 1%, set from the panel. The 1 kVA has an IEC C14 inlet and 6 × IEC C13 outlets; the 2–3 kVA have an IEC C20 inlet and 6 × C13 + 1 × C19 outlets.
Answered on IST8
What installation conditions does the IST8 need?
Leave at least 300–500 mm around the UPS and 500 mm above it, on a flat surface with no vibration and a gradient of not more than 5°. It operates from 0 to 60 °C (best 0–40 °C, output derated from 40 to 60 °C), with an input breaker of 1.5–2 times the maximum input current and no leakage protection.
Answered on IST8
IST8: how big is each model and how much does it weigh?
Width × depth × height and weight, model by model:
| Model | Size | Weight |
|---|---|---|
| IST8-11 | 438 × 423 × 86 mm (2U) | 8.9 kg |
| IST8-2 | 438 × 570 × 87 mm (2U) | 13.6 kg |
| IST8-3 | 438 × 570 × 87 mm (2U) | 16.1 kg |
Unless marked: size and weight from the EMEA 2026 catalogue.
1 Size from AEC's CAD drawing, weight from the EMEA 2026 catalogue.
Each model's own page, linked in the table, gives its full answer and data.
Which outlets does the IST8-2 have?
Six IEC C13 and one IEC C19 at the output, and an IEC C20 inlet. The catalogue advises against inductive or half-wave rectified loads such as motors, air conditioners or fluorescent lamps.
Answered on IST8-2
What heat does the IST8-3 give off at full load?
At 3 kW and 93% efficiency the losses are about 0.23 kW (3 × (1/0.93 − 1)), heat the cabinet ventilation has to remove. Keep 300–500 mm free around the UPS and 500 mm above it, as the catalogue asks.
Answered on IST8-3
Communication and monitoring 2 questions
Can the IST8 be monitored over SNMP?
Yes: USB with power management software is standard, and the intelligent slot (DB9, RS232 + dry contact as shipped) takes an optional SNMP card for remote monitoring and ON / OFF over the network. An RS485 and dry-contact card is also available, and an EPO connector is standard.
Answered on IST8
Can the IST8-2 be monitored over the network?
Yes, with the optional SNMP card in the intelligent slot: input and output voltage and frequency, load and remote ON / OFF. USB with the power management software is standard; an RS485 + dry-contact card is the other option.
Answered on IST8-2
Warranty, service and maintenance 1 question
What warranty does the IST8-1 have?
The EMEA catalogue gives 5 years on the lithium batteries (IST8, All-in-One) and L6 cabinets and 3 years on AEC UPS, extendable with a maintenance contract. AEC confirms the terms with the order.
Answered on IST8-1